Access from the user program
KL31x2
51
Version: 2.4.0
Bit
Name
Description
Default
R37.1
SkipFIR
0
bin
FIR filter is active.
0
bin
1
bin
FIR filter is bypassed.
R37.0
Fast
0
bin
Fast Step Mode is not active.
0
bin
1
bin
Fast Step Mode is active: a fast reaction will follow jumps at
the input, in spite of the filter stage being active. In this case
the filter is bypassed!
Examples
Value in R37
F
Stop
Cycle time
0x35C0
50 Hz
140 ms
0x2660
70 Hz
100 ms
0x1330
140 Hz
50 ms
0x7FF1
40 ms
0x3FF1
20 ms
0x1001
<4 ms
Value in R37
F
Limit
Cycle time
0x7FF2
39.6 Hz
40 ms
0x3FF2
77.36 Hz
20 ms
0x1002
158 Hz
<4 ms
R40: Calibration interval
This register contains the calibration interval for the terminal's automatic calibration. The unit is 100 ms. The
automatic calibration can be activated through bit
in the feature register.
R44: Forced calibration interval
This register contains the interval for the terminal's forced calibration. This interval is always a multiple (the
default is 3
dec
) of the calibration interval. (
). The interval for forced calibration when the terminal
leaves the factory is therefore 3 x 180 s = 540 s. The forced calibration can be activated through bit
in the feature register.
R47: Number of stable measured values
This register contains the number of stable measured values recorded during the calibration.
R48: Tolerance for measured value stability
This register contains the specified stable measured value tolerance.