Product overview
KL3208, KL3228/KS3228
13
Version: 3.3.0
2.3
Technical data
Technical data
KL3208-0010
KL3228-0000 / KS3228-0000
Inputs
8
Sensor types
PT1000 (default)
Ni1000
NTC: 1.8k, 2.2k, 3k, 5k, 10k, 20k, 100k
Poti/Resistor: 6 kΩ, 65 kΩ, 655 kΩ
PT1000 (default)
Ni1000
Wiring
2-wire
1-wire
Terminal points
High Density (HD)
standard (KL), pluggable (KS)
Temperature range Pt sensors
-50°C…+150°C
Ni sensors
-50°C…+150°C
Conversion time
app. 1 s
Measuring current
typically 0.5 mA
Resolution
0.01°C per digit
0.1°C per digit
Measuring error (full measuring
range)
-20°C … +60°C: ±0.25°C
(at 25°C ambient temperature)
-50°C … +150°C: ±1.5°C
±1.0°C, depending on wiring
Bit width in the input process image 8 status bytes (optional), 8 data words
Bit width in the output process
image
8 control bytes (optional), 8 data words (optional)
Power supply for the electronics
via the K-bus
Current consumption from K-bus
typically 85 mA
Electrical isolation
500 V (K-Bus/signal voltage)
Weight
app. 75 g
app. 75 g
Dimensions (W x H x D)
app. 15 mm x 100 mm x 70 mm (aligned with: 12 mm)
on 35 mm mounting rail conforming to EN 60715
Pluggable wiring
-
for all KSxxxx terminals
Permissible ambient temperature
range during operation
-25 °C ... +60 °C (extended
temperature range)
0°C ... + 55°C
Permissible ambient temperature
range during storage
-40 °C ... + 85 °C
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27 see also
instructions for enhanced mechanical load capacity [
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approvals / markings
CE, UKCA, cULus, EAC,
CE, UKCA, cULus, EAC,
Ex marking
Standard
Marking
ATEX
II 3 G Ex nA IIC T4 Gc