Access from the user program
KL3208, KL3228/KS3228
45
Version: 3.3.0
Value in R39
Element
Measuring range
R at 25°C
R at 0°C
0x0032
50
dec
NCT1K8
-40°C ... 130°C
1.8 kΩ
4940 Ω
0x0033
51
dec
NCT1K8_TK
-30°C ... 150°C
1.8 kΩ
5200 Ω
0x0034
52
dec
NCT2K2
-50°C ... 130°C
2.2 kΩ
7373 Ω
0x0035
53
dec
NCT3K
-50°C ... 80°C
3.0 kΩ
9822 Ω
0x0036
54
dec
NCT5K
-40°C ... 100°C
5.0 kΩ
16325 Ω
0x0037
55
dec
NTC10K
-30°C ... 150°C
10 kΩ
32650 Ω
0x0038
56
dec
NTC10KPRE
-30°C ... 150°C
10 kΩ
29490 Ω
0x0039
57
dec
NTC10K_3204
-40°C ... 110°C
10 kΩ
27080 Ω
0x003A
58
dec
NTC10KTYP2
-50°C ... 130°C
10 kΩ
32770 Ω
0x003B
59
dec
NTC10KTYP3
-50°C ... 130°C
10 kΩ
29588 Ω
0x003C
60
dec
NTC10KDALE
-50°C ... 130°C
10 kΩ
32660 Ω
0x003D
61
dec
NTC10K3A221
-40°C ... 130°C
10 kΩ
32639 Ω
0x003E
62
dec
NTC20K
-20°C ... 150°C
20 kΩ
70200 Ω
0x0064
100
dec
Poti/resistor, resolution 0.1 Ω / digit
0 ... 6553.5 Ω
-
-
0x0065
101
dec
Poti/resistor, resolution 1 Ω / digit
0 ... 65535 Ω
-
-
0x0066
102
dec
Poti/resistor, resolution 10 Ω / digit
0 ... 655350 Ω
-
-
0x00C8
200
dec
NTC100K
-40°C ... 130°C
100 kΩ
3266 kΩ
0x00FF
255
dec
user-defined NTC
Avoid the mixed operation of low-resistance PT/NI sensors and high-resistance NTC
sensors on one terminal
Due to large differences in the resistances of the sensor types, the mixed operation of low-resis-
tance PT/NI sensors and high-resistance NTC sensors on one terminal should be avoided, since
larger measuring errors can then occur for the PT/NI sensors.
R40: Conversion time for all channels
You can specify the conversion time for all channels of the terminal with register R40 of the first channel
(default: 10
dec
, approx. equal to 120 ms per channel).
R41: B-parameter for user-defined NTC
This register contains the B-parameter of a user-defined NTC (default: 3960
dec
= 0x0F78).
The user-defined NTC can be activated by setting register R39 to 255
dec
.
R42: Resistance at 25 °C for user-defined NTC
The resistance is specified in 10 Ω / digit. 1000
dec
is thus equal to 10 kΩ
(Default: 1000
dec
= 0x03E8).
R43: Reference temperature for user-defined NTC
(Default: 25 °C = 0x0019)
R44: Lower range limit for user-defined NTC
(Default: -40 °C = 0xFFD8)
R45: Upper range limit for user-defined NTC
(Default: 130 °C = 0x0082)