Access from the user program
KL3356
45
Version: 2.3.0
R3: measured value register 3
• Raw data of the converters:
is not set, register R3 shows the strain gauge reference signal.
• Calibration data:
is set, register R3 shows the preload of the reference signal input.
• Calibration counter 1:
is set, register R3 shows the number of measured values that were smaller
than the first measured value.
R4: register page selection register
Other register pages can be accessed by writing into register R4. The value entered into register R4 is
accepted if the desired register page is present. If that is not the case, the previous value is retained.
Register content R4
Register numbers R32 to R63 permit access to
0x0000
Register page 0: Configuration registers R32 to R63
0x0001
Register page 1: 32 words of freely available SEEPROM memory
0x0002
Register page 2: 32 words of freely available SEEPROM memory
0x0003 to 0xFFFF
reserved
R5: measured value register 4
• Raw data of the converters:
is not set, register R5 shows the most recent actual test value.
• Calibration data:
is set, register R5 shows the correction factor for the differential signal (factor
x 10000).
• Calibration counter 2:
is set, register R5 shows the number of measured values that were greater
than the first measured value.
R6: diagnostic register
is placed into register R6.
R7: command register
User code word
For a command to be executed, it is first necessary for the user code word, 0x1235, to be entered
into
.
Command 0x0101: user calibration - offset
The KL3356 uses the entry 0x0101 in register R7 to compensate the user offset. The calibration value is
entered in register
The calibration value is taken account in weight measuring if bit
is set.
Command 0x0102: user calibration - gain
The KL3356 uses the entry 0x0102 in register R7 to compensate the user gain. The calibration value is
entered in register
The calibration value is taken account in weight measuring if bit
is set.
Command 0x0401: manual calibration mode
Manual calibration mode is enabled by entering 0x0401 into register R7. When the terminal has accepted the
value, then setting
Summary of Contents for KL3356