Product overview
KL403x
11
Version: 4.1
2.2
KL403x - Technical data
Technical data
KL4031
KL4032
KL4034
Number of outputs
1
2
4
Power supply
via the K-Bus
Signal voltage
-10 V…+10 V
Load
> 5 kΩ (short-circuit-proof)
Accuracy
± 0.5 LSB linearity error, ± 0.5 LSB offset error
Output error
< ±0.1 % of the end value
< ± 0.10 % (at 0°C to +55°C)
< ± 0.75 % (when the ex-
tended temperature range is
used)
< ±0.1 % of the end value
Resolution
12 bit
Electrical isolation
500 V (K-Bus / signal voltage)
Conversion time
~ 1.5 ms
Current consumption from the K-bus
typically 75 mA
Bit width in the K-bus I/O
Output: 1 x 16 bits of data (1 x
8 bit control/status optional)
Output: 2 x 16 bits of data (2
x 8 bit control/status optional)
Output: 4 x 16 bits of data (4 x
8 bit control/status optional)
Configuration
No address or configuration settings
Weight
approx. 85 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Permissible ambient temperature range
during operation
0°C to + 55°C
-25°C to +60°C (extended
temperature range)
0°C to + 55°C
Permissible ambient temperature range
during storage
-25°C to +85°C
-40°C to +85°C
-25°C to +85°C
Permissible relative air humidity
95%, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27, see also
Installation instructions for enhanced
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
,GL
CE, cULus,
CE, cULus,