Mounting and wiring
KL403x
22
Version: 4.1
3.5
KL4031, KL4032 - connection and LED description
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
Fig. 11: KL4031, KL4032 - connection and LEDs
KL4031 connection
Terminal point
No.
Comment
Output
1
+ Output
n.c.
2
not used
GND
3
Internal ground (internally connected to terminal point 7)
Shield
4
PE contact (internally connected to terminal point 8)
n.c.
5
not used
n.c.
6
not used
GND
7
Internal ground (internally connected to terminal point 3)
Shield
8
PE contact (internally connected to terminal point 4)
KL4032 connection
Terminal point
No.
Comment
Output1
1
+ Output 1
n.c.
2
not used
GND
3
Internal ground (internally connected to terminal point 7)
Shield
4
PE contact (internally connected to terminal point 8)
Output2
5
+ Output 2
n.c.
6
not used
GND
7
Internal ground (internally connected to terminal point 3)
Shield
8
PE contact (internally connected to terminal point 4)
Summary of Contents for KL403 Series