Product Overview
KL8001 and KL9060
11
Version: 2.0.0
Flashing Code
If there is a fieldbus error, the
stop
LED indicates a flashing code that describes the fault more accurately:
The LED flickers for about 2 seconds before starting the error output. After a clearly visible pause, the error
code is indicated through slow flashing, and the error argument is then indicated after a further pause. The
following table allows you to determine the error more precisely with the aid of these two items of
information.
Code
Argument
Description
Solution
1
0
No rated current set: both the two rotary switches and
• the register PR33 are zero (
not active) or
• at least one of registers PR33, PR39 or PR45 is
zero (single-phase analysis is active)
• Use the
to set a rated
current, or
• enter values for the rated current in
registers
and
.
2
n
Communication with the nth ADC is faulty
Contact your supplier.
3
n
Communication with the n
th
Hall sensor is faulty
Note
Changing the terminal registers
ü
To ensure that the new values are applied to the measuring unit after the terminal regis-
ters have been changed, you have to perform:
a) a power-off reset (switch the terminal off and back on again) or
b) a
(via the command register)!