Technical data, mounting, wiring
PS1021-2405-0000
17
Version: 1.0
3.7
Efficiency and losses
AC 100V
AC 120V
AC 230V
Efficiency
Typ.
90.7%
91.2%
92.3%
At 24 V, 5 A
Average efficiency
*)
Typ.
89.2%
89.4%
90.6%
25% at 1.25A, 25% at 2.5A,
25% at 3.75A. 25% at 5A
Losses
Typ.
1.4W
1.5W
0.7W
At 24 V, 0 A
Typ.
7.0W
7.4W
6.0W
At 24 V, 2.5 A
Typ.
12.3W
11.6W
10.0W
At 24 V, 5 A
*)
The average efficiency is based on assumptions for a typical application with the power supply unit
operating at 25% of the nominal load during 25% of the time, 50% of the nominal load during 25% of the
time, 75% of the nominal load during 25% of the time and 100% of the nominal load during the remaining
time.
Fig. 7: Efficiency over output current; losses over output current
Fig. 8: Efficiency over input voltage; losses over input voltage