Technical data, mounting, wiring
PS1021-2405-0000
23
Version: 1.0
3.13
Environment
Environment
Operating temperature
1)
-10°C to +70°C
Reduction of the output power according to
Fig.
Output current over ambient temperature
Storage temperature
-40°C to +85°C
For storage and transport
Output load reduction
3W/°C (+55°C to +70°C)
For AC 110-120 / 220-240V mains
4)
3W/°C (+50°C to +70°C)
For AC 100 / 200V mains
4)
Humidity
2)
5 to 95% r.h.
According to IEC 60068-2-30
Oscillation, sinusoidal
3)
2–17.8Hz: ±1.6mm;
17.8-500Hz: 2g 2 hours/axis
According to IEC 60068-2-6
Impacts
3)
30g 6ms, 20g 11ms 3 impacts/
direction, 18 impacts in total
According to IEC 60068-2-27
Installation altitude
0 to 2000m
Without restrictions
2000 to 6000m
Reduce output power or ambient
temperature, see Fig.
Output current over
installation altitude
IEC 62103, EN 50178, overvoltage category
II
Load reduction due to
installation altitude
7.5W/1000m or 5°C/1000m
Above 2000m, see Fig.
Output current over
installation altitude
Overvoltage category
III
According to 62103, EN 50178, for altitudes
up to 2000m
II
Altitudes from 2000m to 6000m
Degree of pollution
2
According to IEC 62103, EN 50178, non-
conductive
LABS-free
The device does not release any silicones or other paint-wetting impairment
substances and is suitable for use in paint shops.
1)
The working temperature is identical to the room temperature or the ambient temperature and is defined as
the air temperature 2cm below the device.
2)
Do not energize when condensation is present
3)
Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of
1.3mm and standard mounting position.
4)
For AC 208V mains, AC 200-220V values must be used.
Fig. 11: Output current over ambient temperature; output current over installation altitude