Operation
EL6910
118
Version: 1.8.0
The customization can also be carried out during the download of the safety application.
In order to be able to perform a customization, the groups must be set accordingly. This is done via the
group properties.
Fig. 165: Properties of the TwinSAFE group
If one of the Customizing parameters (
Passification Allowed, Permanent Deactivation Allowed
or
Temporary
Deactivation Allowed
) is set to TRUE, all outputs of the TwinSAFE group that are not Safety Alias Devices
are listed in the list of
Replacement Values
. Here you can parameterize the substitute values to be written to
the output in the event of deactivation of the group.
Fig. 166: Replacement values for the TwinSAFE group
When the Customizing function
is selected, the login dialog opens for the user to enter their login data.
This login must give permission for customizing.