Operation
EL6910
40
Version: 1.8.0
Parameter Description
User inter-
action re-
quired
Conn. no.
Connection number - automatically assigned by the TwinCAT system
No
Conn ID
Connection ID: preallocated by the system, but can be changed by the user. A
Conn ID must be unique within a configuration. Duplicate connection IDs result in
an error message.
Check
Mode
FSoE master: EL6910/EJ6910 is FSoE master for this device.
FSoE slave: EL6910/EJ6910 is FSoE slave for this device.
Check
Watchdog
Watchdog time for this connection. A ComError is generated if the device fails to
return a valid telegram to the EL6910/EJ6910 within the watchdog time.
Yes
Module
Fault is
ComError
This checkbox is used to specify the behavior in the event of an error. If the
checkbox is ticked and a module error occurs on the Alias Device, this also leads
to a connection error and therefore to disabling of the TwinSAFE group, in which
this connection is defined.
Yes
ComErrAck If ComErrAck is linked to a variable, the connection must be reset via this signal in
the event of a communication error.
Yes
Info data
The info data to be shown in the process image of the EL6910/EJ6910 can be
defined via these checkboxes. Further information can be found in the
documentation for
TwinCAT function blocks for TwinSAFE Logic terminals
.
Yes
The EL6910/EJ6910 support activation of a ComErrAck at each connection. If this signal is connected, the
respective connection must be reset after a communication error via the signal ComErrAck, in addition to the
ErrAck of the TwinSAFE group. This signal is linked via the link button
next to COM ERR Ack. The
following dialog can be used for selecting an alias device. The signal can be cancelled via the
Clear
button in
the
Map to
dialog.
Fig. 26: Selecting an alias device
The safety parameters matching the device are displayed under the
Safety Parameters
tab. They have to be
set correctly to match the required performance level. Further information can be found in the TwinSAFE
application manual.
Summary of Contents for TwinSAFE EL6910
Page 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Page 2: ......
Page 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Page 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Page 137: ...Appendix EL6910 137 Version 1 8 0...