Technical data, mounting, wiring
PS2001-2410-0000
12
Version: 1.0
3.2
DC input
DC input
DC input
Nom.
DC 110-150V ±20%
DC input range
Min.
88-180Vdc
Continuous operation
DC input current
Typ.
2.35A
at 110Vdc, at 24V, 10A
DC input current
Typ.
0.84A
at 300Vdc, at 24V, 10A
Permissible voltage L or N
to earth
Max.
375 Vdc
Continuous according to IEC 62477-1
Turn-on voltage
Typ.
80 Vdc
static
Shut-down voltage
Typ.
70 Vdc
static
Typ.
55 Vdc
Dynamic value for up to 250ms max.
Instructions for DC operation
Fig. 3: Wiring for DC input
• Use a battery or a comparable DC source. Operation on the DC link of frequency converters is not
recommended and may lead to defects or malfunctions.
• Connect the positive pole to L and the negative pole to N.
• Connect the PE terminal to the protective conductor or machine ground.