Technical data, mounting, wiring
PS2001-2410-0000
22
Version: 1.0
3.13
EMC
The power supply is suitable for application in industrial environments as well as in residential, commercial
and light industrial areas and small businesses.
The device was tested according to EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-6-4.
EMC interference immunity
Strong transients
VDE 0160
Over the entire load
range
750V, 0.3ms
EMC interference emission
According to the generic standards: EN 61000-6-3 and EN 61000-6-4
Cable-related interference emission, input
lines
EN 55011, EN 55015, EN 55022, FCC
Part 15, CISPR 11, CISPR 22
Class B
Cable-related interference emission output
lines
2)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Limit values for the DC current connection
according to EN 61000-6-3 are met
Interference emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
Class A met between 0A and 12A load Class
C met between 6A and 12A load
Class A met between 0A and 12A load Class
C met between 6A and 12A load
Voltage fluctuations, flicker
EN 61000-3-3
Requirements met
1)
This device complies with FCC Part 15.
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must be
able to deal with any interference received, including interference that may cause undesired operation.
1)
Tested with constant current loads, non-pulsating
2)
For information only, not mandatory for EN 61000-6-3
Switching frequencies
PFC converter
110kHz
fixed frequency
Main converter
84kHz to 140kHz
Output load dependent
Auxiliary converter
60kHz
fixed frequency