Technical data, mounting, wiring
PS2001-2410-0000
24
Version: 1.0
3.15
Protective functions
Protective functions
Output protection
Electronically protected against overload, no load and short circuits. If the electronic output
fuse is activated, an audible noise may occur.
Output overvoltage protection
Typ. 30.5Vdc
Max. 32Vdc
In the event of an internal power supply fault, a redundant circuit
limits the maximum output voltage. The output switches off and au-
tomatically tries to switch on again.
Protection class
IP 20
EN/IEC 60529
Ingress protection
> 4mm
e.g. screws, small parts
Overtemperature protection
Yes
Output shutdown with automatic restart. The temperature sensor is
installed at critical components within the device and switches off
the device in safety-critical situations (e.g. load reduction require-
ments not met, excessive ambient temperature, ventilation blocked
or load reduction not observed if the mounting direction is different).
There is no correlation between the operating temperature and the
switch-off temperature, since the latter depends on the input volt-
age, the load and the installation type.
Protection against input transients
MOV (metal oxide varis-
tor)
Input fuse
Included
Non-replaceable slow-blow fuse with high load capacity
3.16
Safety features
Safety features
Input/output isolation
Double or reinforced electrical isolation
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
Protection class
I
PE (protective conductor) connection required
Insulation resistance
> 500MOhm
Under given conditions between input and output, measured with
500Vdc
> 500MOhm
Under given conditions between input and protective conductor,
measured with 500Vdc
> 500MOhm
Under given conditions between output and protective conductor,
measured with 500Vdc
> 500MOhm
Under given conditions between output and DC OK contacts, mea-
sured with 500Vdc
PE resistance
< 0.1Ohm
Resistance between the protective conductor connection and the
housing near the DIN rail mounting bracket.
Leakage current
Typ. 0.14mA / 0.36mA
At 100Vac, 50Hz, TN, TT / IT network
Typ. 0.20mA / 0.50mA
At 120Vac, 60Hz, TN, TT / IT network
Typ. 0.33mA / 0.86mA
At 230Vac, 50Hz, TN, TT / IT network
Max. 0.18mA / 0.43mA
At 110Vac, 50Hz, TN, TT / IT network
Max. 0.26mA / 0.61mA
At 132Vac, 60Hz, TN, TT / IT network
Max. 0.44mA / 1.05mA
At 264Vac, 50Hz, TN, TT / IT network