SETPOINTS
PRIDE@ VOLTAGE
&
FREQUENCY
RELAY
SINGLE-PHASE
K-0 2 90
If you
� net
order the M-0297/M-0397 Field Adjustment Unit installed in the
PRIDE,
ignore the right
hand column below and fill in the setp:>int values for the functions shown in the left-hand column.
Your settings will then
te
programmed into the
PRIDE
at the factory.
If you
�
order the M-0297/M-0397 to allow the setpoints
to te
field adjustable, a set of fixed backup
settings is also programmed into the
PRIDE to te
used if the Field Adjustment Unit is later removed.
If �he FACTORY SETTINGS shown in the right-hand column are acceptable, you need not fill out the
aJS"IDIIER =m:;s.
O therwise, fill in the desired settings in the left-hand column.
The
OVervoltage
and Undervoltage setpoints are not adjustable using the M-029 7/M-0397 and must
te
supplied by the user.
UND ERVOL TAG E SETPO INT
% of 120 V *
Must be supplied by user
OVERVOLTAG E SETPOINT
% of 1 2 0 V *
Must be suppl ied by user
UNDER FREQUENCY
HZ
OVER FREQ UENCY
HZ
UND ERVOL TAG E TRIP TI MER
CYC
OVERVOLTAG E TRIP
CY C
UND ER FREQUEN CY TRIP TIMER:
CY C
OVER FREQ UEN CY TRIP
CY C
RECONNECT
SEC
RELAY CON F IGURATION
YES
STANDARD
ALTERN ATE
PULSE
NO
59 HZ
6 1
HZ
3 0 CY C
10 CY C
3 0 CY C
30 CY C
1 SEC
YES
NO
x
x
x
•
NOTE,
*
The O v e rvol t a g e s e t point must b e a t l east 3 % hig h e r than t h e
Undervoltage setpoin t , i.e., the minimum voltage bandwidth is 3 % total. If
using an i n put vol ta g e o t h e r than 12 0 V (i . e . , 115
V),
pl ease c o n v e r t
percentages to a base voltage o f 120
V.
Y our Purchase O rder N O
105
www
. ElectricalPartManuals
. com