M-3425 Instruction Book
6–44
81
Frequency (#1, #2, #3, #4)
VOLTAGE INPUTS: Configuration V1
CURRENT INPUTS: None
TEST SETTINGS:
Pickup
P
Hz
(50 to 67)
Time Delay
D
cycles
(2 to 65,500)
Programmed Outputs
Z
OUT
(1 to 8)
Function 24, 27TN, 81R
Disable
■
■
■
■
■
NOTE: It would be efficient to disable the functions with the settings nearest to nominal frequency first
(testing over or underfrequency functions).
1.
Disable functions as shown. See Section 3.2, Initial Setup Procedure/Settings, Configure Relay
Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 designated above. See Section 6.1, Equipment/Test Setup for
configuration.
4.
Pickup Test: Set the voltages V
A
, V
B
, and V
C
to nominal voltage (nominal frequency). For
overfrequency testing, hold the TARGET RESET button in and slowly increase the frequency on
the input voltage(s) until the appropriate FREQUENCY/ROCOF 81/81R LED light goes on or the
pickup indicator operates on the computer target screen. The level will be equal to P Hz ±0.02 Hz
only if P is within 3 Hz of F
nom,
otherwise,
"
0.1 Hz. Return to nominal input frequency and
OUTPUT LEDs will go out. Press TARGET RESET button to remove targets. For underfrequency
testing, decrease the input frequency and return to nominal after operation.
5.
Time Test: With output contacts (Z) connected to stop the timer, apply (P+ or – 0.5) Hz and start
timing. The contacts will close after D cycles within
"
2 cycles or
"
1%, whichever is greater.
6.
Complete the testing for all 81 functions by repeating the appropriate steps for each one.
7.
If testing is complete, enable any functions disabled for this test. If other tests are to be
completed, check the proper functions to disable for the next test and proceed from this point.
Summary of Contents for M-3425
Page 1: ...Instruction Book M 3425 Generator Protection ...
Page 14: ... 13 M 3425 Generator Protection Relay Figure 1 External Connections ...
Page 33: ...x M 3425 Instruction Book This Page Left Intentionally Blank ...
Page 89: ...M 3425 Instruction Book 2 52 This Page Left Intentionally Blank ...
Page 125: ...1 3 A B C M 3425 Instruction Book 4 26 This Page Left Intentionally Blank ...
Page 187: ...M 3425 Instruction Book 6 50 This Page Left Intentionally Blank ...
Page 207: ...M 3425 Instruction Book C 4 This Page Left Intentionally Blank ...
Page 209: ...D 2 M 3425 Instruction Book Figure D 1 Volts Hz 24 Inverse Curve Family 1 Inverse Square ...
Page 210: ...Inverse Time Curves Appendix D D 3 Figure D 2 Volts Hz 24 Inverse Family Curve 2 ...
Page 211: ...D 4 M 3425 Instruction Book Figure D 3 Volts Hz 24IT Inverse Curve Family 3 ...
Page 212: ...Inverse Time Curves Appendix D D 5 Figure D 4 Volts Hz 24IT Inverse Curve Family 4 ...
Page 215: ...D 8 M 3425 Instruction Book Figure D 5 Definite Time Overcurrent Curve ...
Page 216: ...Inverse Time Curves Appendix D D 9 Figure D 6 Inverse Time Overcurrent Curve ...
Page 217: ...D 10 M 3425 Instruction Book Figure D 7 Very Inverse Time Overcurrent Curve ...
Page 218: ...Inverse Time Curves Appendix D D 11 Figure D 8 Extremely Inverse Time Overcurrent Curve ...
Page 223: ...D 16 M 3425 Instruction Book This Page Intentionally Left Blank ...