Installation – 5
5–9
20.
Press
ENTER
to display the nominal
system frequency:
FREQUENCY BUS 1
60.00 Hz
21.
Press
ENTER
for the unit to display the
rate of change frequency:
RATE OF CHANGE FREQUENCY
Hz/Sec
22.
Press
EXIT
for the unit to display
FREQUENCY STATUS
volt curr FREQ powr
J
23.
Press right arrow button once so that
unit displays:
POWER STATUS
volt curr freq POWR
J
24.
Press
ENTER
to display real power and
verify the correct polarity. The polarity
should be positive for forward power
and negative for reverse power. If the
readings do not agree with actual
conditions, check the polarities of the
three low end CT’s and /or the PT’s and
the CT and PT ratios.
REAL POWER
PU
W
25.
Repeat steps for the remaining metering
quantities.
REACTIVE POWER
______ PU ______ VAr
APPARENT POWER
______ PU ______ VA
POWER FACTOR
______ Lag/Lead
13.
Press
ENTER
to display line currents (I
A,
I
B,
I
C
). Compare these currents with the
measured values using a meter. If there
is a discrepancy, check the CT
connections to the rear terminal block
of the unit. The unit should display:
PHASE CURRENT
A= B= C=
14.
Press
ENTER
for the unit to display
neutral current. The neutral current
should be near zero amperes.
NEUTRAL CURRENT
Amps
15.
Press
ENTER
for the unit to display
positive sequence current. The positive
sequence current should be I
POS
y
I
A
y
I
B
y
I
C
.
POS SEQUENCE CURRENT
Amps
16.
Press
ENTER
for the unit to display
negative sequence currents. Negative
sequence current should be near zero
amperes.
NEG SEQUENCE CURRENT
Amps
17.
Press
ENTER
for the unit to display the
zero sequence currents. The zero
sequence should be I
ZERO
y
0.00. If
there is a significant amount of negative
or zero sequence (greater than 25% of
I
A
, I
B
, or I
C
) then either the phase
sequence or the polarities are incorrect.
Modify connections to obtain proper
phase sequence and polarity.
ZERO SEQUENCE CURRENT
Amps
18.
Press
EXIT
for the unit to display :
CURRENT STATUS
volt CURR freq powr
J
19.
Press right arrow button once so that
unit displays:
FREQUENCY STATUS
volt curr FREQ powr
J
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...