M-3520 Instruction Book
6–32
67DT Phase Directional Overcurrent, Definite Time
VOLTAGE INPUTS:
V1
CURRENT INPUTS:
C1
TEST SETTINGS:
Pickup
P
Amps
(1.0 to 240.0)
1 Amp
(0.2 to 48.0)
Directional
See Below
Three Phase Detect
See Below
Delay
D
Cycles
(1 to 8160)
MSA
MSA
Degrees
(0 to 359)
Programmed Outputs
Z
Output
(1 to 8)
Function 32
Disable
Function 47 #1, #2
Disable
Functions 50, 51V, 59
Disable
Functions 67IT, 67NDT, 67NIT
Disable
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 and C1 designated above. Refer to Section 6.1, Equipment/Test
Setup for configurations.
4.
Single-Phase Pickup Test
: Disable Directional and Three-Phase Detect features, if enabled. Apply
Nominal Voltage to all three phases. Apply current 10% less than pickup (
P
) to all three phases. Hold
the
TARGET RESET
button in and slowly increase the current applied to phase A until the
DIR
PHASE DEF TIME O/C 67DT
LED lights, or the pickup indicator operates on the computer target
screen. The level should be equal to
P
amps ±0.1 Amps or
&
3%. Release the
TARGET RESET
button and decrease phase A current and the
OUTPUT
LED will go out. Press the
TARGET RESET
button again to remove targets. If desired, repeat this test for both phase B and C currents.
5.
Three-Phase Pickup Test
: Enable the Three-Phase Detect feature and perform test #4 again to
verify that the relay does not operate. Reset targets and apply Nominal Voltage to all three phases.
Apply current 10% less than pickup (
P
) to all three phases. Hold the
TARGET RESET
button in and
slowly increase the current applied to all phases until the
DIR PHASE DEF TIME O/C 67DT
LED
lights, or the pickup indicator operates on the computer target screen. The level should be equal to
P
amps
&
0.1 Amps or
&
3%. Release the
TARGET RESET
button and decrease the applied current
and the
OUTPUT
LED will go out.
6.
Directional Test
: Reset targets and apply Nominal Voltage to all three phases. Set the current angle
to an angle more than 100° from
MSA
. Apply current 10% more than pickup (
P
) to all three phases.
Hold the
TARGET RESET
button in and slowly swing the angle of the currents applied toward
MSA
until the
DIR PHASE DEF TIME O/C 67DT
LED lights, or the pickup indicator operates on the
computer target screen. The angle should be equal to
A
–90° or +90°, depending to which side of
MSA
the current has been set. Release the
TARGET RESET
button and swing the current angle
away from
MSA
, and the
OUTPUT
LED will go out.
7.
Timer Test
: Disable the Directional and Three-Phase Detect features, if enabled. Apply Nominal
Voltage to all three phases. Apply current 10% less than pickup (
P
) to all three phases. With output
contacts connected to a timer, apply
P
+10% Amps and start timing. The contacts will close after
D
cycles within –1 to +3 cycles or
&
3%.
8.
If testing is complete, enable any functions disabled for this test. If other tests are to be completed,
check the proper functions to disable for the next test and proceed from this point.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...