–3–
M-3520 Intertie Protection Relay
STANDARD FUNCTIONS
Device
Setpoint
Number
Function
Ranges
Increment
Accuracy
†
Sync Check
Sync Check
Sync Check
Sync Check
Sync Check
Phase Angle Window
0° to 90°
1°
&
1°
Upper Voltage Limit
60 to 140 V
1 V
&
0.5 V or
&
0.5%
Lower Voltage Limit
40 to 120 V
1 V
&
0.5 V or
&
0.5%
Delta Voltage Limit
1.0 to 50.0 V
0.1 V
&
0.5 V
Delta Frequency Limit
0.001 to 0.500 Hz
0.001 Hz
&
0.0007 Hz or 5%
Sync Check Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Dead Voltage Limit
0 to 60 V
1 V
&
0.5 V
Dead Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Sync Check may be operated as a stand-alone function or supervised by 79 (reconnect). Various combi-
nations of input supervised hot/dead closing schemes may be selected.
Undervoltage
Undervoltage
Undervoltage
Undervoltage
Undervoltage
Pickup #1, #2
5 to 180 V
1 V
&
0.5 V or
&
0.5%
&
0.8 V or
&
0.75%*
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
* When line-ground to line-line is selected.
Neutral Undervoltage
Neutral Undervoltage
Neutral Undervoltage
Neutral Undervoltage
Neutral Undervoltage
Magnitude
5 to 180 V
1 V
&
0.5 V or
&
0.5%
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
Reverse/Forward Power
Reverse/Forward Power
Reverse/Forward Power
Reverse/Forward Power
Reverse/Forward Power
Pickup #1, #2
-3.000 to +3.000 PU
0.001 PU
&
0.002 PU or 2%
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
+16 Cycles or
&
1%
The per-unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings.
Single phase detection may be selected for line-to-ground connected VTs. This function can be selected as
either overpower or underpower in the forward direction (positive setting) or reverse direction (negative setting).
Negative Sequence Overcurrent
Negative Sequence Overcurrent
Negative Sequence Overcurrent
Negative Sequence Overcurrent
Negative Sequence Overcurrent
Definite Time
Pickup
0.10 to 20.00 A
0.01 A
&
0.1 A or
&
3%
(0.02 to 4.00 A)
(
&
0.02 A or
&
3%)
Time Delay
1 to 8160 Cycles
1 Cycle
–1 to + 3 Cycles or
&
3%
Inverse Time
Pickup
0.50 to 5.00 A
0.01 A
&
0.1 A or
&
3%
(0.10 to 1.00 A)
(
&
0.02 A or
&
3%)
Characteristic Curves
Definite Time/Inverse/Very Inverse/Extremely Inverse/IEC Curves
Time Dial
0.5 to 11.0
0.1
&
3 Cycles or
&
5%
0.05 to 1.10 (IEC curves)
0.01
Negative Sequence Overvoltage
Negative Sequence Overvoltage
Negative Sequence Overvoltage
Negative Sequence Overvoltage
Negative Sequence Overvoltage
Pickup #1, #2
5 to 180 V
1 V
&
0.5 V or
&
0.5%
Time Delay #1, #2
1 to 8160 Cycles
1 Cycle
–1 to +3 Cycles or
&
1%
27
46
47
†
Select the greater of these accuracy values.
Values in parentheses apply to 1 Amp CT secondary rating.
25
27G
32
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...