2–15
Application - 2
25 DEAD INPUT ENABLE
i6 i5 i4 I3 i2 i1
25 DEAD DELAY
________ Cycles
Externally controlled dead closing.
Dead delay timer setting.
Phase Angle Window:
Upper Voltage Limit:
Lower Voltage Limit:
Sync Check Delay:
Dead Voltage Limit:
Dead Time Delay:
#1
@ : WARNING, Function DISABLED until output selected!
(25) - SYNC CHECK
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
FL
6
5
4
3
2
1
Input Initiate
Delta Voltage:
Enable
Disable
Delta Frequency:
0.001 Hz
0.500 Hz
Enable
Disable
Dead V1 Hot V2
Hot V1 Dead V2
Dead V1 Dead V2
Supervised by Function 79
Save
Cancel
0
o
60 V
40 V
1 Cycle
0 V
1 Cycle
90
o
140 V
120 V
8160 Cycles
60 V
8160 Cycles
1.0 V
50.0 V
Figure 2-8
M-3822 IPScom
®
for Windows™ Sync Check (25) Setpoint Ranges
Path
: Relay Menu/Setup/Setpoints/(25) Sync Check
COMMAND BUTTONS
Save
Saves all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...