2–31
Application - 2
59G/27G Overvoltage/Undervoltage, Neutral
Circuit or Zero Sequence
The neutral Overvoltage/Undervoltage functions 59G/
27G provide protection for ground faults on the
system.
Save
Cancel
@ : WARNING, Function DISABLED until output selected!
(59G) - NEUTRAL OVERVOLTAGE
Pickup:
Delay:
5 V
1 Cycle
180 V
8160 Cycles
#1
OUTPUT
8
7
6
5
4
3
2
1
FL
6
5
4
3
2
1
Blocking Input
@
Figure 2-21
M-3822 IPScom
®
for Windows™ Neutral Overvoltage (59G) Setpoint Ranges
Path
: Relay Menu/Setup/Setpoints/(59G) Neutral Overvoltage
COMMAND BUTTONS
Save
Saves all information to the relay.
Cancel
Returns the user to the previous window; any changes to the displayed information are lost.
Applications of 59G/27G, shown in Figures 2-27 and
2-28, are for detecting ground faults on the utility
side of the power transformer. Protection schemes
are applied based on using one or three voltage
transformers (VT).
27G PICKUP
________ Volts
27G DELAY
________ Cycles
59G PICKUP
________ Volts
59G DELAY
________ Cycles
If these functions are enabled, the following settings are applicable:
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...