M-3520 Instruction Book
5–8
8.
Press
ENTER
to display positive
sequence voltage. The positive
sequence voltage should be V
POS
y
V
A
y
V
B
y
B
C
y
or V
AB
y
V
BC
y
V
CA
.
POS SEQUENCE VOLTAGE
Volts
9.
Press
ENTER
to display negative
sequence voltage. The negative
sequence voltage should be V
NEG
y
0.
NEG SEQUENCE VOLTAGE
Volts
10.
Press ENTER to display zero
sequence voltage. The zero sequence
voltage should be V
ZERO
y
0.
ZERO SEQUENCE VOLTAGE
Volts
■
■
■
■
■
NOTE:
If negative sequence voltage shows a
high value and positive sequence
voltage is close to zero, the phase
sequence may be incorrect. Proper
phasing must be achieved to obtain
proper readings. If phase sequence is
incorrect, frequency related functions
will not operate properly and the
FREQUENCY STATUS
menu will read
DISABLED
.
If positive, negative and zero sequence voltages
are all present, check the polarities of VT
connections and correct the connections to obtain
proper polarities.
11.
Press
EXIT
. The unit will display:
VOLTAGE STATUS
VOLT curr freq powr
J
12.
Press the right arrow once, so that
the unit displays:
CURRENT STATUS
volt CURR freq powr
J
5.4
Commissioning Checkout
During field commissioning, perform the following
procedure to ensure that the CT and VT connections
are correct.
1.
On the keypad, press
ENTER
. After a
short delay, the unit should display:
VOLTAGE RELAY
VOLT curr freq pwr
J
2.
Press the right arrow button until the unit
displays:
STATUS
I
config sys STAT
J
3.
Press
ENTER
. The unit should display:
VOLTAGE STATUS
VOLT curr freq powr
J
4.
Press
ENTER
to display the phase
voltages. The unit should display either
V
A
V
B
, V
C
, for line-to-ground connections
or V
AB,
V
BC,
V
CA
, for line-to-line
connections). Use a voltmeter to compare
these actual measurements. If there is a
discrepancy, check for loose connections
to the rear terminal block of the unit.
PHASE VOLTAGE
AB= BC= CA=
5.
Press
ENTER
to display the peak phase
voltage.
PEAK PHASE VOLTAGE (PU)
AB= BC= CA=
6.
Press
ENTER
to display the neutral
voltage. Neutral voltage should be V
N
=0
Volts
NEUTRAL VOLTAGE
Volts
7.
Press
ENTER
to display V2 phase
voltage.
PHASE VOLTAGE (V2)
Volts
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...