Chapter 4
Software Configuration
30
Bedrock Secure OSA Remote User Manual - BRDOC020_001
10/11/18
Voltage Input Levels and
Thresholds
Table 4-2 shows the input voltage levels that are selectable in the Bedrock IDE
along with the corresponding thresholds for on and off voltage levels for each
setting.
Input Options and Sensor
Types
Table 4-3 lists the type of input sensors and the input range of those sensors
available on the OSA Remote.
Line Frequency Options
Line frequency options are configurable to accommodate different locales. The
supported line frequency options for the OSA Remote are:
•
50 Hz
•
60 Hz
Analog to Digital Sampling
Rates
The analog to digital converter sampling rates and resolutions available for the
OSA Remote in the Bedrock IDE are shown in Table 4-4. The sampling rates
available are dependent on the line frequency and are measured in samples per
second (SPS).
Table 4-2 Input Voltage Settings and Thresholds
Input Voltage Setting
Off Voltage
On Voltage
5 V DC
2 V
4 V
12 V DC
6 V
8 V
24 V DC
12 V
14 V
Table 4-3 Input Sensor Types and Ranges
Sensor Type
Actual Input Range
4-20 mA
3.25-22 mA
0-10 V
0.1-12 V