Chapter 4
Configuration and Status
24
Bedrock SPS.500 User Manual - BRDOC125_007
9/3/21
Configuration Data
The information shown when the Configuration tab is selected is described in
Table 4
-
2.
Software Version
SPS firmware version
Bootloader Version
Version of the Bootloader
Time Stamp
Time of last update of SPS data
Power Values Group
Input Voltage
Voltage on the AC input of the SPS
Input Current
Current on the AC input of the SPS
Input Power
Power on the AC input of the SPS
Output Voltage
Voltage on the 24 V output of the SPS
Output Current
Amount of load current in amps
Output Power
Output power from the SPS
Efficiency
Measured efficiency of the SPS
Line Frequency
Measured input frequency
“OR”ing Current
Measured current of the “OR”ing output
Temperatures Group
CPU Temperature
Measured temperature of the CPU
Converter Temperature
Measured temperature of the switching converter
Table 4
-
1 SPS.500 States, Power Values, and Temperatures
Group/Group Member
Description
Table 4
-
2 SPS.500 Configuration Data
Group/Group Member
Description
SPS On
Select to turn the SPS on.
SPS Auto Start On
SPS output will be turned on immediately when
power applied.
“OR”ing Controller On
Select to enable the “OR”ing controller on the SPS.
Output Voltage
Sets the SPS output voltage.
When under load, the output voltage should not be
adjusted in increments greater than one volt in order
to avoid voltage dips.
DC Overcurrent Limit
Exceeding this value (specified in amps) on the
primary output will result in an overcurrent condition.
See below for more information on overcurrent
behavior.
“OR”ing Overcurrent Limit
Exceeding this value (specified in amps) on the
“OR”ing output will result in an overcurrent condition.
See below for more information on overcurrent
behavior.