Configuration and Status
Chapter 4
9/3/21
Bedrock SPS.500 User Manual - BRDOC125_007
33
Logged Events
The events listed in Table 4
-
7 are logged by the SPS.500. The event name and
event data appear in the log entry.
Table 4
-
7 SPS.500 Logged Events
Event Name
Event Reason
Additional Event Data
Power Up
System is reset
Reset cause
Configuration Change
System configuration has been updated
For each system configuration parameter
that changes, the following values will be
sent.
First value (16 bytes): IPv6 address of the
system that made the change
Second value: 32
-
bit index indicating the
changed parameter. Possible value are
listed in the following table.
Third value (32 bits) is the previous value of
the changed parameter.
Fourth value (32 bits) is the new value of
the changed parameter.
Client Connect
Connection was accepted via OPC UA or
Bedrock IDE
IPv4 or IPv6 address of the client
Client Disconnect
Connection was terminated via OPC UA or
Bedrock IDE
IPv4 or IPv6 address of the client
Authentication Failure
A client attempting a connection has failed
to authenticate
IPv4 or IPv6 address of the client plus the
subject name sent by the client
Log Erase
The log was erased. The Log Erase entry
will be the first entry in the log after a Log
Erase event
IPv6 address of the client that requested
the log erase
System Time Set
The system time has been set
Following 32
-
bit fields.
Current (previous) time seconds
Current (previous) time nanoseconds
New time seconds
New time nanoseconds
IPv6 address of the client
Fault Reset
A fault has caused the SPS.500 to reset
Fault that caused the reset
Reset Latch Off
User has selected the Overcurrent Latch
Off checkbox
IPv6 address of the client
RTC Not Valid
Real-time clock value not valid. This event
only occurs at power up
SPS.500 revision B or later