Configuration and Status
Chapter 4
9/3/21
Bedrock SPS.500 User Manual - BRDOC125_007
35
Additional Items Logged by the SPS.500
Table 4
-
10 lists additional items that are logged by the SPS. The log entry text
and associated data appear in the log entry. Items listed in the table include
warnings and informational messages.
Over Temperature
An over
-
temperature condition has been
detected
Fault data including source and
temperature as follows:
First value: 8-bit value that can be one of
the following:
5=CPU
6=PFC
Second value: 8-bits, always 0
Third value: 32-bit temperature (°C),
floating point
“OR”ing Output
Overcurrent Fault
The load on the “OR”ing output is greater
than the configured ORing Overcurrent
Limit
“OR”ing output current in amps
Total Output Overcurrent
Fault
The sum of the load on the primary output
and “OR”ing output is greater than the
configured Total Overcurrent Limit
Total output current in amps
Table 4
-
9 SPS.500 Logged Faults
Fault Name
Fault Reason
Additional Fault Data
Table 4
-
10 Additional SPS.500 Logged Items
Log Entry Text
Reason
Additional Data
Output Overcurrent
Warning
The load on the output is greater than the
configured Overcurrent Warn threshold
Output current in amps
“OR”ing Output
Overcurrent Warning
“OR”ing Output is enabled and a current
greater than the configured Overcurrent
Warning threshold is detected on the ORing
output
“OR”ing output current in amps
Total Output Overcurrent
Warning
The sum of the load on the primary output
and “OR”ing output is greater than the
configured Total Overcurrent Warning
threshold
Total output current in amps