INSTRUCTIONS

IMPORTANT SAFEGUARDS 

When using electrical equipment, basic safety precautions should always be followed including the following: 

1.  READ AND FOLLOW ALL SAFETY INSTRUCTIONS 

2.  Disconnect power before performing work on electrical equipment. 
3.  Do not use outdoors. 
4.  Do not let power cords touch hot surfaces and do not mount near gas or electric heaters. 
5.  Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or 

eyes, flush with fresh water and contact a physician immediately. 

6.  Equipment should be mounted in locations and/or at heights where unauthorized personnel will not readily subject it 

to tampering. 

7.  The use of replacement parts or accessory equipment not furnished by Beghelli, may cause equipment failure and 

will void the warranty.

8.  Do not use this equipment for other than its intended purpose. 
9.  Servicing of this equipment should be performed by qualified service personnel. 

10. SAVE THESE INSTRUCTIONS!

OVERVIEW 

AC Input

120/208/277V

AC Output

120/208/277V

Lighting

Load

Test

Button

Transformer

Transformer

Inverter Box

N-ON / N-OFF

Switch

Batteries

NO transformer if both input and output voltages are 120V
Batteries MUST be connected for Inverter to turn ON

N-ON

 (Normally ON): unit will always provide AC output to lighting load when AC input is available, and during AC input failure

N-OFF

 (Normally OFF): unit will provide AC output to lighting load only when AC supply input fails

MAXIMUM SURGE VALUES: Inrush / Peak current factor of the lighting load should be considered while sizing 

lighting load for the inverter

•  Nova UAC-P 

6000W for 0.1 second

This unit is 

FLOOR MOUNT ONLY!

CAUTION 

1.  Verify on Lighting load wiring that the 

neutral

 conductor 

IS NOT BONDED OR CONNECTED

 to the 

ground wiring

.

2.  Inverter’s AC output MUST be wired by its own line and neutral wires. 

DO NOT connect the AC output neutral wire 

to any neutral wires in the building

3.  If more than one inverter is installed, DO NOT CONNECT the neutrals of multiple AC outputs together. 
4.  DO NOT CONNECT the AC output line and neutral to the mains AC input line and neutral. 
5.  Observe battery polarity. RED is “+” POSITIVE and BLACK is “-” NEGATIVE. 
6.  The battery charging current has been factory set. DO NOT adjust it. 
7.  Disconnect 

ALL

 electrical sources including the inverter’s AC and DC inputs before servicing.

Beghelli U.S.A., 3250 Corporate Way, Miramar, Florida, Tel: (800) 726-4316 Tel: (954) 442-6600 Fax: (954) 442-6677

926000443

11/28/2017

Nova UAC (NV-UAC-P)

Pure Sine Wave

1500 or 2000W