7
BL3300 SERIES MANUAL 01/28/2013
SECTION 2
UNPACKING AND INSTALLATION
2.4
3 PHASE INPUT POWER REQUIREMENTS
( continued )
The chart below indicates the proper fuse based on the model number of the power supply. This chart can
also serve as a guide for sizing the input service to the unit. Note: refer to the following section for C8/9
singe phase units.
The following lists should be used to select the proper line fuse size for the model numbers shown. The
selections are based on nominal line voltages and maximum output power. All fuses carry a 600 Vac rating.
DO NOT
substitute any other fuse type.
MODEL #
L-L VOLTAGE
FUSE SIZE
PART NUMBER
BL 3XXX - C2
380V
12 AMP / 600V
108-201-021
BL 3XXX- C3
480V
10 AMP/ 600V
108-201-020
BL 3XXX- C5
600 V
10 AMP/ 600V
108-201-020
BL 3XXX- C6
400V
12 AMP/ 600V
108-201-020