P1351ser.wpd
5-2-2
1.3
EIA-232 SERIAL COMMUNICATION
The Power Supply receives ASCII encoded command strings via a EIA-232 interface according to
MATE System Control Interface Standard No. 2806763 (IEEE-716 CIIL). The AC Power Supply
supports all OPCODES, NOUNS, and MODIFIERS required by the stimulus module. They are as
follows:
OPCODES
FNC, FTH, :CHO, SET, SRX, SRN, CLS, OPN, RST, CNF, IST,STA INX,
MODIFIERS
FREQ, VOLT, CURR, VLT0, VLT1
NOUN
ACS
The P1351 Series Power Supply can be used in point-to-point mode where a host
Computer is connected directly to One Power Supply.
NOTES:
1. Leading zeroes must be entered for commands.
2. Leading zeroes are blanked in response transmit.
Table 5-2-1
CILL SOFTWARE COMMANDS
CIIL COMMANDS
EXPLANATION
SET VOLT <value>
Sets output voltage to given value,in volts rms. The following values are
permitted:
0 < value < 135, or 270, dependent on range selected and type of unit.
SET FREQ <value>
Optional. The following values are permitted:
45 < value < 500.
Default is 45 Hz only if SET FREQ, SRN FREQ, or SRX FREQ are not
received. Otherwise the values shall be used in the order stated.
SRX VOLT <value>
Optional. Sets maximum limit for SET VOLT command. If SET VOLT value
is greater than SRX VOLT value in a command string, an error message is
generated and the setup command ignored. The following values are
permitted:
0 < value < 135, or 270, dependent on range selected and type of unit.
If a value for SRX VOLT is not specified, the required maximum value for
SET VOLT default to 135, or 270, dependant on range selected and type of
unit.