background image

Foreword

Installation manual for T15BR

Foreword

All operator panels are developed to satisfy the demands of human-machine
communication. Built-in functions such as displaying and controlling text,
dynamic indication, time channels, alarm and recipe handling are included.
The operator panel works primarily in an object-oriented way, making it easy to
understand and use. Configuration is carried out on a PC using the iX Developer.
The project can then be transferred and stored in the operator panel itself.
Various types of automation equipment such as PLCs, servos or drives can be
connected to the operator panels. In this manual, the term “the controller” refers
to the connected equipment.
This manual explains how to install the operator panel. Please refer to the
iX Developer reference manual for further information.

Order no: MAEN165

Copyright © 2014-04 Beijer Electronics AB. All rights reserved.

The information in this document is subject to change without notice and is provided as available at the

time of printing. Beijer Electronics AB, including all its group companies, reserves the right to change any

information without updating this publication. Beijer Electronics AB, including all its group companies,

assumes no responsibility for any errors that may appear in this document. Read the entire installation

manual prior to installing and using this equipment. Only qualified personnel may install, operate or repair

this equipment. Beijer Electronics AB, including all its group companies, are not responsible for modified,

altered or renovated equipment. Because the equipment has a wide range of applications, users must acquire

the appropriate knowledge to use the equipment properly in their specific applications. Persons responsible

for the application and the equipment must themselves ensure that each application is in compliance with

all relevant requirements, standards and legislation in respect to configuration and safety. Only parts and

accessories manufactured according to specifications set by Beijer Electronics AB, including all its group

companies, may be used.

BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP
COMPANIES, SHALL NOT BE LIABLE TO ANYONE FOR ANY
DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL
DAMAGES RESULTING FROM THE INSTALLATION, USE OR
REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT,
CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL
BE THE REPAIR, REPLACEMENT, OR REFUND OF PURCHASE
PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL
BE AT THE SOLE DISCRETION OF BEIJER ELECTRONICS AB,
INCLUDING ALL ITS GROUP COMPANIES.

Beijer Electronics, MAEN165

Summary of Contents for 640003701

Page 1: ...T15BR Installation Manual English MAEN165 2014 04...

Page 2: ...group companies assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only quali ed personnel may i...

Page 3: ...rals 11 3 TechnicalData 12 4 ChemicalResistance 14 4 1 MetalCasing 14 4 2 Touch Screen and Overlay 15 4 2 1 Auto ex EB 15 4 2 2 Touch Screen Surface 16 4 2 3 Touchscreen Protective Film 16 4 3 Termina...

Page 4: ...powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of water and get medical attention The gures in this manualserves a...

Page 5: ...ow the table with cable and torque speci cationsbelow Terminal Block Connector Wire Size TQ Lb In Phoenix Contact Part No 1757022 14 20 AWG 2 08 0 52 mm2 5 7 Warning Do not open when an explosive atmo...

Page 6: ...ccompanyinginstallation instructions Onlyquali ed personnel may install the operatorpanel Separate the high voltage signal and supply cables Make sure that the voltage and polarity of the powersource...

Page 7: ...onment lithiumbattery electrolytic capacitorand display 1 8 Appearance of Air in Touch Screen The layerstructure of the touch screen contains airandinrare casesappearance of bubbles can arise This is...

Page 8: ...ce Requirements Maximum installation plate thickness 8 mm Space requirements in millimeterswhen installingthe operatorpanel 100 100 100 50 50 410 286 Note The dimensions on the drawing are not proport...

Page 9: ...rawingis available for download from the Beijer Electronics web site Formore information see sections Operator Panel Drawings and Technical Data 3 Secure the operator panel in position by screwingthe...

Page 10: ...from signal and supply cables Shielded communication cables are recommended 24V DC RS232 RS422 RS485 24V DC A D Controller Power B Ethernet C Use 14 20 AWG 2 08 0 52 mm2 wire forthe powerconnections C...

Page 11: ...chthem tostrain reliefplate with cable ties provided 2 2 3 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurth...

Page 12: ...pin D sub contact with RS232 RTS CTS chassis mounted female with standard locking screws 4 40 UNC Communication module CAN Ethernet 1 x 10 100 1000 Base T shielded RJ45 1 10 100 Base T shielded RJ45...

Page 13: ...sistance for more information 2 Standby mode The backlight is turned off there are no cabled interfaces and the CPU is below 5 Optional CAN module is present 3 Typical mode The backlight is fully powe...

Page 14: ...chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Sodium hypochlorite Turpentine Note If exposure to any of...

Page 15: ...60 95 1 Bleach 1 Hydrochloric acid 36 Sulfuric acid 10 Castor oil Linseed oil Tomato ketchup Caustic soda 40 1 Methanol Trichloroaceticacid 50 Cutting oil Nitric acid 10 White Spirit Cyclohexanol Par...

Page 16: ...play protection lm thatcan be ordered from BeijerElectronics Outdoor Use In common with all polyesterbased lms Auto exEB is not suitable foruse in conditions oflong term exposure todirect sunlight Not...

Page 17: ...to the following chemicalsat room temperature Acetic acid conc Na hypochlorite 10 Ammonia 30 Nitric acid 10 Butanol Phosphoric acid 10 Ethyl acetate Phosphoric acid 20 Hydrochloric acid 37 cold Note...

Page 18: ...USB 2 USB Host 2 0 max output current 500 mA 5 Headphone Headphone Connector 6 LAN B 1 x 10 100 1000 Base T shielded RJ45 7 COM 2 RS422 RS485 Communication Port 5 2 Communication Ports Serial port 9 p...

Page 19: ...5 3 T15BR Outline 286 410 7 max 8mm 76 9 9 392 9 268 9 B C E D A E A Connectors B SD memory card slot C USB host D Expansionport E Optional CAN module not shown CAN depth doesnotexceed heatsink Beijer...

Page 20: ...cordingto localelectrical codes between the operatorpanel s quick connect plinth and the panel s chassis see 2 in drawing above 2 Connect awire orgroundingbraidthat is sized correctly accordingto loca...

Page 21: ...5 RJ45 RJ45 RJ45 Industrial Ethernet Operator panel Operator panel Operator panel Operator panel Shielded Short and unshielded 0 1 F 250 V 1 1 3 3 8 8 2 2 In some industrialunits forEthernet the RJ45...

Page 22: ...istobreak the shield see 3 in drawing above A more elegant methodistoexpand the shielded Ethernet cablingwith a piece of unshielded Ethernetcable see 4 in drawingabove The shield canbe grounded via a...

Page 23: ...shield to the ground via a 0 1 F 250 V plastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms ofLF thus avoidingthe 50 60 Hz gro...

Page 24: ...to heat The lifespan of an electrolytic capacitoris cut in halfwith an 8 10 C increase in temperature A 15 20 C temperature increase resultsin a quarter of the lifespanetc Rittal has a goodprogram for...

Page 25: ...Vaccording to EN 60950 protection against electric shock andUL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay co...

Page 26: ...al Many peripherals includingUSBdevices will bond the terminal s signal ground 0 V to the protective earth ground Bonding signal ground and protective earth ground mayincrease electricalemissions and...

Page 27: ...the ground potential the shield should be connected tothe ground via 0 1 F 250 V plastic capacitorto preventground current in the braided shield A numberof manufacturers recommendthat the shield be g...

Page 28: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Reviews: