General Specification
2.2.1.
General Specification
General specification
System Power
Supply voltage: 24Vdc nominal
Supply voltage range : 15~32Vdc
Protection: Output current limit (Min. 1.5A)
Reverse polarity protection
Power Dissipation
70mA typical @ 24Vdc
Current for I/O Module
1.5A @ 5Vdc (When using in ‘60
℃
~ 70
℃
’ temperature environment,
the power dissipation is limited to 0.8A.)
Isolation
System power to internal logic : Non-isolation
System power I/O driver : Isolation
Field Power
Supply voltage : 24Vdc typical (Max. 32Vdc)
* Field Power Range is different depending on IO Module series.
Refer to IO Module`s Specification.
Max. Current Field Power Contact DC 10A Max
Weight
162g
Module Size
54mm x 99mm x 70mm
Environmental specification
Operating Temperature
60
℃
~ 70
℃
: Power dissipation is limited to 0.8A.
-40
℃
~ 60
℃
: 1.5A full load is allowed.
UL Temperature
-20
℃
~60
℃
Storage Temperature
-40
℃
~85
℃
Relative Humidity
5% ~ 90% non-condensing
Mounting
DIN rail
* When using Ethernet/IP only, tcp timeout connection time value should be ‘0’. ‘0’ value means tcp
connection time out is disabled. Refer to ‘Adapter TCP/IP Special Register (0x1040, 4160)’ at section ‘
3.3.3’
** When using in ‘60
℃
~ 70
℃
’ temperature environment, the power dissipation is limited to 0.8A.