4.5.
Motor Terminal Box Connections
Most general purpose motors are wound for operation on dual voltage supplies. This is indicated on the nameplate of the motor
This operational voltage is normally selected when installing the motor by selecting either STAR or DELTA connection. STAR always gives the
higher of the two voltage ratings.
Incoming Supply Voltage
Motor Nameplate Voltages
Connection
230
230 / 400
Delta
400
400 / 690
400
230 / 400
Star
4.6.
Motor Thermistor Connection
Where a motor thermistor is to be used, it should be connected as follows :-
Additional Information
Compatible Thermistor : PTC Type, 2.5kΩ trip level
Use a setting of P1-13 that have Input 5 function as External Trip, e.g. P1-
13 = 6. Refer to section
Error! Reference source not found.
for further
etails.