User Guide Revision 1.12
49
10.
Digital Input Functions
10.1.
Digital Input Configuration Parameter P1-13
P1-13
*(2)
Local (Hand)
Control Function
Digital Input 1
(Terminal 2)
Digital Input 2
(Terminal 3)
Digital Input 3
(Terminal 4)
Analog Input 1
(Terminal 6)
Analog Input 2
(Terminal 10)
Notes
0
N/A
All functions User defined in Menu 9 or configured through PLC function in OptiTools studio software
suite.
1
*(3)
Analog Input 2
O: Stop
C: Run / Enable
O: Normal Operation
C: Preset 1 / PI Set-point
2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
When Input 3 is Closed:
Speed Reference =
Analog Input 2
Start Command = Input 1
In PI Mode, Analog Input
1 must be used for
feedback
2
O: No Function
C: Momentary Start
O: Stop (Disable)
C: Run Permit
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
3
O: Stop
C: Run / Enable
O: Forward
C: Reverse
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
4
O: Stop
C: Run / Enable
O: Fire Mode
*(1)
C: Normal Operation
* (1)
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
5
Preset Speeds
O: Stop
C: Run / Enable
O: Preset Speed 1
C: Preset Speed 2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Ext Trip
C: Normal Operation
When Input 3 is Closed:
Speed Reference =
Preset Speed 1 / 2
Start Command = Input 1
6
O: No Function
C: Momentary Start
O: Stop (Disable)
C: Run Permit
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Preset 1
C:Preset 2l
7
O: Stop
C: Run / Enable
O: Forward
C: Reverse
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Preset 1
C:Preset 2
8
O: Stop
C: Run / Enable
O: Fire Mode
*(1)
C: Normal Operation
* (1)
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Preset 1
C:Preset 2
9
*(3)
Keypad Speed
Reference
O: Stop
C: Run / Enable
O: Normal Operation
C: Preset 1 / PI Set-point
2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
When Input 3 is Closed:
Speed Reference =
Keypad
Start Command =
Determined by P2-37
10
*(3)
O: Stop
C: Run / Enable
O: Normal Operation
C: Preset 1 / PI Set-point
2
O: Remote Ctrl
C: Local Ctrl
Analog In 1
O: Ext Trip
C: Normal Operation
11
O: No Function
C: Momentary Start
O: Stop (Disable)
C: Run Permit
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
12
O: Stop
C: Run Fwd
O: Forward
C: Reverse
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
13
O: Stop
C: Run Fwd
O: Fire Mode
*(1)
C: Normal Operation
* (1)
O: Remote Ctrl
C: Local Ctrl
Analog In 1
Analog In 2
Notes
*(1): Logic shown is as per the default setting. Fire mode logic can be configured through parameter P8-09.
*(2): Default setting for P1-13 = 1
*(3): When the drive is in PID control (P1-12 = 3) and digital preset reference is selected (P3-05 = 0) then P1-13 can be set to 1, 9, or 10 to allow
selection between two independent digital references using digital input 2. Digital preset reference 1 and 2 are set in P3-06 and P3-15
respectively.
Note: “Motor thermistor trip” connection is via analog input 2 and is configured by parameter P2-33 (
). The “External trip” input is no
longer utilised for the thermistor input (this is different to the ODP drive and E2 drive).