Settings in the programming tool
19
Beijer Electronics
Connection via coaxial cable
In the network the coaxial cable RG58 is used. Bus endings of 50 Ohm must be
used. Several coaxial cables can be connected with repeaters in order to use
longer networks. The network will then comprise different segments.
The maximum length of a segment is 185 m, with a maximum number of 30
units in each segment. Four repeaters can be serial connected, which means that
five segments may be serial connected. Only three of the segments can have units
connected. This means that there must be at least two empty segments in the
network. The RG58 network cable must be grounded in one side.