Always take care to ensure a proper weight balance before lifting and moving unit.

 

 

2.1.2 

  

机组的拆箱

Unpacking of Unit

 

拆箱后,检查机组及其他备件是否有任何损坏,如发现任何损坏,请及时联系百尔。

 

When unpacking, inspect for any damage to packing material or the unit itself which may affect 

the unit’s performance. If any such damage is evident, please contact your local Beijer Ref branch.

 

 

2.1.3 

  

机组的放置与固定

   

Installation Location (Refer to the General Arrangement Drawing section)

 

如果机组放置在靠近墙壁的场所或者密闭通道内,需要确保机组能获得足够的风量,以供风量的的畅通及机

组的维修。机组必须牢固地安装在坚固水平的地面上,以防止它掉下或翻倒。 

尤其是要保证机组有一个通畅的环境,以阻止冷凝机组排放出的热空气回流。 

压缩机冷凝机组须用相应的地脚螺栓水平固定在基础上。

 

机组的供液管路均装有视液镜,在机组运行时,应留有足够的空间来观察视液镜。 

If  the  unit  is  to  be  located  in  close  proximity  to  a  wall  or  similar  obstruction,  the  minimum 

distance from the coil face to the obstruction shall comply with the general arrangement drawing. The 
unit shall be mounted on a horizontal plane surface.

 

   It  is  particularly  important  for  the  units  to  allow  sufficient  unobstructed  air-discharge  space  in 

front of the unit to prevent warm air recirculation to the condenser

 

   

Condensing Unit should be properly installed on horizontal base with corresponding foot bolts.

 

  The liquid  sight  glass is  located inside the unit. Allow sufficient  space around the access  panels 
for opening the panels

 

2.1.4 

 

系统充注

System Holding Charge

 

系统在出厂时均充注干燥空气或氮气。 

如果收货验收时发现系统未经充压,请及时联系百尔制冷公司。 
将系统预先充注的气体以适当的方式排出。在制冷系统中选择合适的排气位置。 

机组在试运行之前需将系统中的压力抽空至 200 微米以下。 

The system as supplied is pressurised at the factory with Dry Air or Nitrogen gas. 
   If the system is not pressurised on delivery, please contact your Beijer Ref branch.  
  Care  must  be  taken  to  release  the  pressure  before  attempting  to  gain  access  to  any  part  of    the 
refrigeration system. 
  The unit should be evacuated to a pressure of 200 microns (μmHg) prior to commissioning.

 

 

2.1.5 

压力设置

  

Pressure Settings

 

风冷冷凝机组的最大运行压力为

29bar

,这主要取决与压力容器(储液器)的限制。因此卸压装置的压力应小

29bar

。压力开关的设置,如高压侧压力必须小于

26bar

 

建议

卸压装置设置应不大于

0.9

倍最高工作压

力。“精锐”风冷机组最大设计的冷凝温度为

60

℃。当使用

HP

控制设备时,必须考虑到使用制冷剂的类型以

及环境的最高温度。

 

“SLIM  POWER”  condensing  units  have  a  maximum  operating  pressure  of  29  Bar(g) 
determined  on  pressure  vessels  (such  as  liquid  receivers).  Thus  any  pressure  relief  device 
setting must be 29 bar(g) or lower.  
Pressure limiting device settings such as the HP control  must be  26 Bar(g) or lower. Adviced 
that  the  pressure  limiting  device  setting  is  no  greater  than  0.9  times  the  maximum  operating 
pressure

.  

Summary of Contents for SLIM POWER

Page 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Page 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Page 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Page 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Page 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Page 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Page 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Page 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Page 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Page 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Page 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Page 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Page 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Page 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Page 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Page 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Page 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Page 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Page 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Page 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Page 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Page 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Page 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Page 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Page 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Page 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...