EN: 

 

 

 

 

14 

 

Refrigeration  piping  work  shall  be  carried  out  professionally  by  qualified  refrigeration  mechanics  in 
accordance  with  applicable  national  and  local  regulations  and  in  conformance  with  good  engineering 
practices required for the proper operation of the refrigeration system.

 

 

百尔生产的压缩冷凝机组有较高的洁净度和干燥度,并且系统内部充注了干空气或氮气,可以防止氧化和

湿气及异物的进入。 管道在安装时应格外小心,减小管道安装的时间可以防止湿气或异物的进入。 

内部相连的制冷管道的大小不必与机组的出口管道大小一致。 管道尺寸的选择/计算是基于确保最小制冷

剂压降和有效回油最低制冷剂流速。百尔公司可提供相应的管道尺寸计算的技术支持。 

水平吸气管与机组连接的时候应有适当的坡度,使油因为重力而自由返回压缩机。1:100 的坡度是比较合

适的。竖直段管道必须使用回油湾及双立管。吸气管道应有保温措施,减小过热影响。 

如果在安装时有任何疑问,请向当地的销售代表咨询。 

All  Centurion  condensing  units  manufactured  by  Beijer  Ref  are  supplied  clean  and  internally 

charged with dry air or nitrogen to prevent oxidation and ingress of moisture or foreign matter. Care 
shall be taken during installation of the piping to prevent entrance of foreign matter or moisture by 
minimizing the time that the piping is uncapped. 

The interconnecting refrigeration pipe size is not necessarily the same size as the outlet on the 

unit.  The  pipe  sizes  shall  be  selected/calculated  based  on  the  best  compromise  of  minimizing 
refrigerant pressure drop and refrigerant velocity to ensure efficient oil return. 

Horizontal  suction  lines  shall  slope  towards  to  the  units  to  allow  the  oil  return  freely  to  the 

compressor by gravity. A 1:100 slope is considered sufficient. The use of oil trap and double risers 
may  be  necessary  on  vertical  sections.  Suction  line  piping  shall  be  insulated  to  minimize  the 
superheat effect to the vapour. 

If  in  doubt  during  the  installation,  please  consult  with  your  local  sales  representatives 

and/or application engineers from Beijer Ref for technical support. 

2.3 

压缩机启动

Compressor Starting

 

    

对于较大型的压缩机启动时产生的瞬间起动电流要格外小心。

 

 

Care should be taken to  establish starting requirements for the larger compressors due to high in-

rush current.

 

2.4    

冷凝风扇控制

Condenser

 

Fan Controller

 

     

“精锐”冷凝机组可选配冷凝风扇控制器。

 

使用

R404A

制冷剂时,推荐设定值为

:

单风扇

11 Bar(g)

,双风扇

11 Bar(g) 

14Bar(g)

 

R22

制冷剂时,推荐设定值为

:

单风扇

9 Bar(g)

,双风扇

9 Bar(g) 

12Bar(g)

 

Condenser Fan controller is option for “SLIM POWER” condensing unit. 
For R404A refrigerant, recommended setting : 11Bar (g) for 

single fan

, 11Bar (g) and 14Bar (g) 

for dual fan. 

For R22 refrigerant, recommended setting : 9 Bar (g) for 

single fan

, 9Bar (g) and 12Bar (g) for 

dual fan.

 

 

警告

——其他制冷剂的设置

Warning

——Setting for other refrigerant

 

对于不是使用本系列样本所示制冷剂的机组,安装者有义务对其进行合理设置

 

The installer has a duty to make reasonable settings for the unit, which used none-catalogue refrigerant

.

 

 
 
 

Summary of Contents for SLIM POWER

Page 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Page 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Page 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Page 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Page 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Page 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Page 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Page 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Page 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Page 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Page 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Page 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Page 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Page 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Page 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Page 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Page 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Page 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Page 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Page 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Page 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Page 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Page 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Page 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Page 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Page 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...