EN: 

 

 

 

 

18 

 

5、设备推荐安装在走廊尽头、空旷区域、卫生间或其它对噪音不敏感区域; 

1.

 

Equipment is prohibited to be installed in flammable, explosive, steam, hot air or fume waste gas; 

2.

 

If install in the corrosive gas around, need to be customized; 

3.

 

Whether it is indoor or “SLIM POWER” unit, the installation space must have enough air flow and 
good ventilation conditions, to avoid air short cycle, and is strictly prohibited in the confined space; 

4.

 

Installed away from the noise sensitive areas, and to take proper account of the shock absorption and 
sound insulation measures, to avoid vibration and noise into the building; 

5.

 

Recommended to install in the end of the corridor, open area, bathroom or any nose insensitive area

 

3.1.2  

位置要求

Location requirements

 

1

、所选择的设备安装位置,其基座、地面、支撑物或地基必须足够牢固,并能支持设备的重量;

 

2

、建议采取必要的措施防止地面积水对机组的危害;

 

3

、设备安装时应在周围留有足够的空间,便于机组的通风及日常的维护保养或维修工作,具体参考尺寸请见

3.2

 

4

、对于多台设备安装在一起的情况,必须合理布置,避免相互之间的气流干扰形成短循环;

 

5

、为保证机组的安全及寿命,建议安装在阴凉遮阳的地方;

 

1.

 

The installation position, base, ground, or foundation must be strong enough to support the weight of 
the equipment; 

2.

 

Take the necessary measures to avoid the ponding damage to the unit; 

3.

 

Space  around unit should be enough, for easy ventilation and daily maintenance, for specific 
dimension, please refer to 3.2; 

4.

 

For a number of equipment installed in the case, must be reasonable layout, to avoid mutual 
interference to air flow of unit; 

5.

 

To ensure the safety and life of the unit, recommended to install in a shade place

 

3.1.3  

配电要求

Distribution requirements

 

1

、设备尽量使用专用电源,避免和其它用电设备共用;

 

2

、客户应提供足够的配电容量;

 

1.

 

Special power supply is recommended, avoid to sharing with other electric equipment; 

2.

 

Power distribution capacity should be enough

 

3.2  

外形尺寸

Dimensions

 

3.2.1  

外形尺寸表(表中单位:

mm

Dimensions

unit

mm

 

 

机组型号

Model

 

安装孔长

Mounting 
Hole Length

 

安装孔宽

Mounting 
Hole Width

 

LxWxH 

BD020MZ2*D  BDX020LZ2*D-AG 

585 

388 

1032x425x845 

BD030MZ2*D  BDX030LZ2*D-AG 

585 

388 

1032x425x845 

BD040MZ2*D  BDX040LZ2*D-AG 

585 

388 

1032x425x845 

BD050MZ2*D  BDX050LZ2*D-AG 

585 

388 

1032x425x1245 

BD060MZ2*D  BDX060LZ2*D-AG 

585 

388 

1032x425x1245 

BD075MZ2*D  BDX075LZ2*D-AG 

585 

388 

1032x425x1245 

 

机组型号

Model

 

 

 

 

Mounting 
Hole Length 

 

 

 

Mounting 
Hole Width 

L x W x H 

BDN020LZ2*D-F 

BDN020LZ2*D 

585 

388 

1032x425x845 

BDN030LZ2*D-F 

BDN030LZ2*D 

585 

388 

1032x425x845 

Summary of Contents for SLIM POWER

Page 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Page 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Page 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Page 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Page 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Page 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Page 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Page 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Page 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Page 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Page 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Page 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Page 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Page 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Page 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Page 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Page 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Page 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Page 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Page 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Page 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Page 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Page 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Page 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Page 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Page 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...