background image

 

“精锐”压缩冷凝机组 

“SLIM POWER”CONDENSING UNIT 

 

 

   

   

   

冷(无

  

锡)有

   

   

   

 

Beijer Ref (Wuxi) Co. Ltd 

PN: 

YAL0002-60 

Issue: 

Date:      01/01/20 
Page:       5 of 26  
EN: 

 

 

 

 

 

1.  

 

警告和预防措施

Warning and Safeguards

 

百尔在设计制造该产品时非常关注安全问题, 但是终端用户, 工程安装商,维护人员在操作设备时也要注意安全。 

Beijer Ref is very conscious of safety issues during designing and manufacturing with refrigerating system, 
We  have  to  ensure  the  end  user,  installer  or  service  personnel  exercises  the  safety  caution  when  working 
with the units. 

 

1.1  

概述

General Notes

 

壁挂室外型风冷冷凝机组是参照 GB/T 21363-2008 生产,只有持相关资质的人员才能进行此类产品的安装

及维修,且安装和维修都应符合当地的规范。 

Beijer  Ref  “SLIM  POWER”  condensing  units  fall  under  the  requirements  for  commercial 

electrical  equipment  as  per  Standards  Beijer  Ref  guidelines.  Installation  and  major  service  of  this 
unit must be carried out by a licensed contractor and in accordance with local regulatory guidelines.

 

1.2 

警告

       

电气连接

 

Warning       Electrical Hazard

 

所有电气操作人员必须持证上岗,并且遵守有关规定执行。

 

在任何情况下,都要首先切断设备的电源,然后才能进行电控箱或其他部件的
操作。

电源线材必须符合

GB5023-2008

 

A qualified Electrician must carry out all electrical work. 

Always isolate the 

power to the unit before checking and / or diagnosing the units. Never 

work on any electrical item without isolating or disconnecting the power supply. 

All field wiring must conform 

to the requirements of the equipment and all applicable National and Local Codes.

 

 
 

1.3 

注意

   

压缩机自动启动和复位

Caution        Compressor Start-Up & Reset

 

压缩机的过载保护功能或高、低压开关起作用时,压缩机的供电电路被切断,压缩机将停止运行,当保护

恢复后,在没有任何警告的情况下压缩机会自动复位或运行。

 

Condenser fans and compressors are thermally protected. When tripped, these components  will not 
operate.  Once sufficiently  cooled, the  component will automatically  reset  and may operate without 
warning. 
The unit is equipped with a High/Low pressure switch as standard. The standard switch is an auto-
reset type on both high and low sides. 

 

警告

 

Warning

 

请特别注意此标识所示内容,忽视其提醒可能会造成人员的伤害或者伤亡。

 

This indicates contents for which, if disregarded, the possibility of human death or 
severe injury can be happened.

 

注意

 

Caution

 

 

请特别注意此标识所示内容,忽视其提醒可能会造成人员的伤害或财产的损失。

 

This indicates contents for which, if disregarded, the possibility of human injury or the 
possibility of material damage can be happened. 

 

 

Summary of Contents for SLIM POWER

Page 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Page 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Page 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Page 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Page 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Page 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Page 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Page 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Page 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Page 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Page 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Page 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Page 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Page 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Page 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Page 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Page 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Page 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Page 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Page 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Page 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Page 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Page 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Page 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Page 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Page 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...