“精锐”压缩冷凝机组 

“SLIM POWER”CONDENSING UNIT 

 

 

   

   

   

冷(无

  

锡)有

   

   

   

 

Beijer Ref (Wuxi) Co. Ltd 

PN: 

YAL0002-60 

Issue: 

Date:      01/01/20 
Page:       6 of 26  
EN: 

 

 

 

 

 

1.4 

注意

   

压缩机

Caution   Compressor

 

对于较大型号的机组,电机启动时可能会影响供电情况,从而导致相邻设备出现故障,一旦出现这种情况,

请向当地的百尔售后服务寻求建议或帮助。

 

High capacity models of the unit, may affecting the due to power supply, resulting unnecessary 

equipment fault, once appear this kind of circumstance, please seek advice or get assistant from your 
local Beijer Ref after-sales service support.

 

1.5 

个人防护设备

Personal Protective Equipment

 

 

建议在机组相关的任何工作情况下(包括维修、安装或拆卸)都应穿上手套,眼罩,耳罩等防护用品,并应

注意以下情况: 

 

压缩机或排汽管的温度很高,接触物体可能会达到物体的着火点而引起火灾。 

 

制冷剂泄漏时,要特别注意对眼睛和皮肤的保护。 

 

如果需要移除制冷剂,请不要直接将其排放到空气中,请用回收装置回收制冷剂。 

Beijer  Ref  recommends  as  a  secondary  safety  precaution  that  all  personnel  working  with  the 

unit wear appropriate Personal Protective Equipment (PPE) such as gloves, eyewear and footwear. 

 

Compressor  or  discharge  pipe  temperature  is  high,  anything  contacted  may  reach  the  ignition 
point to fire.

 

 

Leaking refrigerant, please pay attention to the protection of the eyes and skin.

 

 

When  removing  refrigerant,  refrigerants  cannot  be  vented  into  atmosphere.  Please  reclaim  the  
refrigerants.

 

1.6 

制冷剂回收

Refrigerant Reclaim

 

如果要把设备中的制冷剂排出,应用专门设备收集,不可将制冷剂直接排放到环境中。只有专业技术人员

才有权进行此操作,其他任何人员不得擅自操作。

 

If the refrigerant in the device is discharged, a proper recovery system has to be in place, Do not  

directly  discharged  into  the  environment.  Only  professional  personnel  have  the  right  to  carry  out 
this operation. 

 

 

1.7

 

 

禁止吸烟

No Smoking

 

百尔建议在距离设备 15 米之内严禁吸烟。 

Beijer Ref recommends No Smoking within a distance of 15 metres of the unit. 

1.8 

注意

      

设备充压

Caution

      Unit Pressurized

 

所有机组都预先充注了高压干燥空气或氮气,在对机组进行安装或调试之前,请小心排放出设备中的高压

气体。

 

All units are pressurised with dry air or Nitrogen gas. Care must be taken to discharge the 

pressurized gas prior to installing or commissioning the equipment. 

Summary of Contents for SLIM POWER

Page 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Page 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Page 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Page 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Page 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Page 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Page 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Page 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Page 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Page 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Page 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Page 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Page 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Page 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Page 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Page 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Page 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Page 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Page 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Page 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Page 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Page 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Page 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Page 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Page 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Page 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...