1) When powering on the CO922, you will see that the MAINS LED lights up and starts blinking for about 90 seconds.
Afterward the LED stays on without blinking, the CO922 is ready to detect.

2) Press the button placed on the side the sensor to simulate the presence of gas.
The Led alarm lights up, the relay changes the state of work.
Ceased the alarm, the Led turns off, it stops the sound of the buzzer and the connected devices will be disabled.

Test run with GAS

To test the toxic gas emit gas from a pre-calibrated bottle from 30 to 300 ppm, in the grey sensor, see item 5 (of page
3).
Using other types of gas could damage the sensor.
N.B. This test is recommended to be performed once a year.

Page 6

The position of the detector is a crucial factor for its correct functioning during gas detection. In order to obtain the
maximum results from a device and minimize the probability of false alarms, it is recommended to follow this scheme
and keep in mind the following general regulations. The CO922 is an equipment adapted to be mounted on a wall.
When  installing  is  good  to  use  reasonable  care  that  requires  an  electronic  device,  and  then:
-  Install  the  detector  away  from  sources  of  heat.
-  Avoid  that  the  liquids  may  come  into  contact  with  the  detector,  remembering  that  its  box  has  a  degree  of
protection  IP42.

The  installation  height  of  the  detector  C0922  must  be  from  a  minimum  to  a  maximum  of:
Minimum  160  cm.  from  the  floor

Turn on and testing

Carbon monoxide gas detector
min. 1,60 from the floor

0  15  30  45  60  75  90  105  120 135  150

Clean
 Air

Diagram of detection

G

a

s

 d

e

te

c

ti

o

n

 i

n

 p

p

m

30  ppm  CO
50  ppm  CO
1 00  

pp m

C O
3 00  

pp m

Time in minutes

Installation measures and positioning

Table n° 2 of  EN 50291

“CONDITIONS                   ALARMS ”

30  ppm

120 minutes

50  ppm

60 minutes

100  ppm

10 minutes

300  ppm

within 3 minutes

Concentration  co 

 

         ALARM AFTER

The detector must not be installed
behind the barriers that hinder the
prompt  detection  of  gas  .  near  of
aspirators or fans and in areas where
the temperature falls below 10 ° C or
rises above 40 ° C.

Summary of Contents for CO922

Page 1: ...allation and user guide EN 50291 EN 50270 CEI 216 3 EN 61010 1 Installation EN 60079 29 2 The CO922 detector has been designed and built according to European regulations to detect the presence of CO toxic gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features this detector is suitable for household applicati...

Page 2: ... Power supply 230Vac 50 60 Hz 10 Power consumption 1W Change over relays for CO toxic gas detection 10A 250V resistive Insulation Class II CO toxic gas sensor Electrochemical Cell CO detector alarm sensitivity 30 300ppm CO gas detector alarm threshold according to norm EN 50291 on gas accumulation ALARMS 30 ppm within 120 minutes 50 ppm within 60 minutes 100 ppm within 10 minutes 300 ppm within 3 ...

Page 3: ... to the fault circuit as well as the light indication and a cricket siren 3 CO ALARM indication LED This LED will light up when the gas concentration level has reached the 300ppm concentration or when the accumulation level is reached The relay contact is closed and an impulsive sound is issued 4 Electrochemical Cell sensor for Carbon Monoxide detection 5 TEST button This button is used to simulat...

Page 4: ... The relays are voltage free WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the elec...

Page 5: ... 2 3 4 5 1 2 3 4 5 Solenoid valve NA Fan Fan Power Supply 230 VAC N Ph 1 2 3 4 5 Power Supply 230 VAC Fan Solenoid valve NA N C C NO NC C NO NC C NO One or more detectors with a normally close valve 230VAC Ph N 1 2 3 4 5 1 2 3 4 5 Solenoid valve NC Fan Fan Power Supply 230 VAC NC C NO NC C NO Electrical connections ...

Page 6: ...to follow this scheme and keep in mind the following general regulations The CO922 is an equipment adapted to be mounted on a wall When installing is good to use reasonable care that requires an electronic device and then Install the detector away from sources of heat Avoid that the liquids may come into contact with the detector remembering that its box has a degree of protection IP42 The install...

Page 7: ... does not exempt from the compliance with all regulations concerning the characteristics installation and use of gas appliances the ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 1083 71 and relevant legal provisions 1 Put out all free flames 2 Close the main gas tap or the LPG cylinder tap 3 Do not turn any lights on or o...

Page 8: ...xcluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collect...

Reviews: