CHECK the integrity of the probe after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and as a result of
which BEINAT S.r.l. therefore disclaims any responsibility for possible damages caused to people, animals
or objects.
INSTALLATIONWhen performing the installation, please remind that if you pierce the RGX100 container, it
will lose its properties and its conformity to REGULATIONS.
TERMS and EXPECTATIONS: The installation of the RGX100 detector, its ordinary and extraordinary maintenance,
and its out of service removal at the end of the functional life guaranteed by the manufacturer, must be carried out
by authorized and/or specialized personnel.
Do not allow it to become wet.
The detector can be seriously damaged when immersed in water. Remember that the probe has an IP42 protection
degree..
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the probe could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Absolutely avoid using any cloth dipped in thinners, alcohol and chemical detergents.
Maintenan ce
The user periodically (every 6 months), it must carry out a verification of the detector functioning spraying a
specific gas test into the slots on the front of the device until to get the alarm of the detector.
• At least 1 time a year perform a more accurate control by a specialized technician.
• The disposal of the detector (5 years after installation), It must be carried out by qualified technician
Mains power .............................................................................................. 230VAC 50/60 Hz +/- 10%
Battery power .............................................................................................. 12 VDC – 1.2 Ah +/- 10%
Current consumption ....................................................................................................... 3.1 W @ 230V
Range of relay contact switching ..................................................... 10A 250V resistive - 5A 30Vdc resistive
Battery charger Max ............................................................................... Built in for a 1.2Ah 12VDC battery
Insulation ........................................................................................................................... Class II
Explosive gas sensor .................................................................................................................... Catalytic
Explosive gas detector alarm threshold ............................................................................. At 10% of L.E.L.
Sensor’s faults detected by Fault Circuit ................................................... Interruption, short circuit, or wear
Detection capsule end-of-life warning .................................................................................. After 5 years
Timed functioning solenoid valve only 12 V dc ..................................................................... Internal jumper
Continuous functioning solenoid valve or siren 230 V selection ................................................ Internal jumper
Audible and visual signal alarm by ............................................................................ LED diode and buzzer
Test phase duration ................................................................................................................ 60 seconds
Functioning temperature ................................................................................................. -10°C to +40°C
Functioning humidity ............................................................................................ 0÷90% RH non condensed
External degree of protection ......................................................................................................... IP42
Mounting ................................................................................. External wall mount, or embedded box 503
Body material .......................................................................................................... ABS self-extinguishing
Dimensions ........................................................................................................................... 115x150x52
Technical Specifications
Functional Features Of Gas Sensors
The installation of the RGX100 detector, its ordinary and extraordinary maintenance, and its out of service
removal at the end of the functional life guaranteed by the manufacturer, must be carried out by authorized
and/or specialized personnel.
The CATALYTIC technology sensor duration is guaranteed for 6 years (in clean air).
The detector’s functioning temperature ranges from -10°C to + 40°C.
WARNING!
The CATALYTIC probe does not tolerate a gas detection exceeding 100% of L.E.L., with consequent natural
death of the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing
aerosol.
A common cigarette lighter near the sensor does not guarantee excellent functioning.