background image

Page  6

Currently national standards enforceable in the installation country covering the installation and use of gas powered
equipment are to be respected, as are standards covering smoke dispersion and ventilation of enclosed areas, even
though gas detection equipment is installed.
Essential  element  for  the  correct  functioning  of  the  detector  is  its  correct  installation.
Following  the  suggestions  in  this  section  you  will  get  a  high  accuracy  combined  with  a  total  absence  of  false
alarms.
The  RGX100  is an equipment  adapted  to be mounted  externally on a wall. Installing, it  is  fine to use  ordinary
care  that  requires  an  electronic  device,  and  then:
-  Install  the  detector  away  from  sources  of  excessive  heat.
-  Avoid  that  liquids  come  into  contact  with  the  detector  RGX100,    remembering  that  its  external  structure  has
degree  of  protection  IP42.

The  detector  should  not  be  installed:
-  
in  environments  where  the  temperature  drops  below  10  °  C  or  rises  above  40  °  C.

The  detector  is  equipped  to  detect  different  types  of  gases,  and  according  to  these,  its  must  to  be  positioned
at  different  heights.
These  heights  are:
-  30  cm  from  the  lowest  point  of  the  floor  in  order  to  detect

heavy  gases  (LPG,  etc)

-  30  cm  from  the  highest  point  of  the  ceiling  in  order  to  detect

light  gase  (Methane  etc)

-  Install  detectors  from  1  to  4  m  from  gas  appliances

The installation of the detector does not exempt from ... ... The compliance with all regulations concerning the
characteristics, installation and use of gas appliances. The ventilation of the spaces and the elimination of combustion
products are described in the UNI norms according to ART. 3 LAW 1083 / 71 and relevant legal provisions.

METHANE gas detector
max. 30 cm from the ceiling

LPG gas detector
max. 30 cm from the floor

Installation measures and positioning

Caution!!
Do  not  install  the  detector  near:
sinks,  air  intakes,  heating  or  air
conditioning systems, windows and
ventilation devices.

Summary of Contents for RGX100

Page 1: ...ith the concept of home fitness comes the household gas detector RGX100 detects through the catalytic sensor the presence of explosive gas such as Methane LPG Gas detection The detector is tested and calibrated to 10 of L E L The power supply unit allows driving of a manual reset solenoid valve with a 12Vdc coil without any buffer battery If the voltage absorption is too high you can later integra...

Page 2: ...a specialized technician The disposal of the detector 5 years after installation It must be carried out by qualified technician Mains power 230VAC 50 60 Hz 10 Battery power 12 VDC 1 2 Ah 10 Current consumption 3 1 W 230V Range of relay contact switching 10A 250V resistive 5A 30Vdc resistive Battery charger Max Built in for a 1 2Ah 12VDC battery Insulation Class II Explosive gas sensor Catalytic Ex...

Page 3: ...ds and then will reopen them This is needed to prevent damaging some types of manual reset solenoid valve coils This features is suitable only when a 12 Vdc electrovalve is connected By opening the two poles the relay will be set to continuous functioning 6 Relay This relay changes its position when the detector trigger the main alarm 7 Catalytic sensor for Methane or LPG explosive gas detection 8...

Page 4: ...e free Power supply 230 240 VAC Electrical connections WARNING Before connecting to the mains power ensure the voltage is correct Carefully follow the instructions and the connections according to Regulations in force An automatic disconnetting switch appropriately identified as the detector sectioning device must be incorporated in the electrical system suitably located and easily accessible N C ...

Page 5: ...tery 12VDC 1 2Ah MAX N B The 12VDC voltage can be derived from another source Normaly open solenoid valve 12VDC N C C NO 1 2 3 4 5 6 7 Solenoid valve NA 12 VDC Connection with a normally closed solenoid valve 12 VDC N C C NO N Ph 1 2 3 4 5 6 7 230 240 VAC Solenoid valve NA 12 VDC ATTENTION Relay is voltage free The power supply is 230 240 VAC with a buffer battery 12VDC 1 2Ah MAX N C C NO 1 2 3 4 ...

Page 6: ...r should not be installed in environments where the temperature drops below 10 C or rises above 40 C The detector is equipped to detect different types of gases and according to these its must to be positioned at different heights These heights are 30 cm from the lowest point of the floor in order to detect heavy gases LPG etc 30 cm from the highest point of the ceiling in order to detect light ga...

Page 7: ...oes into alarm and closes the connected equipment Check that connections are correct and that the jumper which leads to the common voltage of the relay has been carried out all the relays are voltage free Check the scheme of connection If RGX100 is connected to a Solenoid valves 12 VDC and does not work To RGX100 you can not connect directly solenoid valves sirens in 12 VDC It must always to use t...

Page 8: ...excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collec...

Reviews: