Installation and user
guide

Important: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.

Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and
keep it for future reference. It is also recommended to perform the electrical connections correctly as
per enclosed drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side

EN 50194
EN 50270

Compliant  EN 60079-29-1

Installation  EN 60079-29-2

Reports issued by  TUV Italia

Channel:  Beinat  gas  solutions

Electric connections also available on

The SGM595 is born from the elegance and prestige that has always distinguished  BEINAT S.r.l. and from the home
fitness  concept.
The  probe is a Catalytic gas detection unit with IP55 protection that, together with one of BEINAT’s industrial type
Control Units, detects the presence of esplosive gas such as Methane, LPG, Hydrogen.

The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to
it, but  also allows execution of a self-diagnosis and therefore an AUTOMATIC  CALIBRATION,

 

in order to always have

the maximum detection accuracy.
The self-calibration means the probe adapts in harsh and variable temperature environments, avoiding false alarms due
to anomalous events.
The probe has a 0 ÷ 20 % LEL linear output conforming to the 4 ÷ 20mA standard, for which can be connected with
one of BEINAT's industrial control units.
The important innovation of this probe is:
The possibility to substitute the sensor at the end of the operating cycle or fault by the technician without having to
send to BEINAT Srl.

Indispensabile instrument for the annual check of the probes

Instrument  of  testing  TS1008
To facilitate the reading of the functional parameters of the probe as well as the control of annual
operating,  the  BEINAT  S.r.l.  has  built  a  new  portable  tester  TS1008.
The tester allows to read all the data in the memory of the probes eand by serial transmission,
it prints the ticket that  confirms the testing data.

                      Conventional Gas Sensor SGM595

                                                                                           V. R1bd04

Summary of Contents for SGM595

Page 1: ...ith one of BEINAT s industrial type Control Units detects the presence of esplosive gas such as Methane LPG Hydrogen The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it but also allows execution of a self diagnosis and therefore an AUTOMATIC CALIBRATION in order to always have the maximum detection accuracy The self calibration means...

Page 2: ... gas by issuing it from a pre calibrated testing aerosol Important The test of operation and eventually offset cancellation must be performed at least once a year by a qualified technician CHECK the integrity of the unit after having removed it from the box Check that the data written on the box correspond to the type of gas used When doing the electrical connections follow the drawing closely Any...

Page 3: ... operation of the control unit by spraying a suitable test gas at the base of the probes connected until the alarm condition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel The position of the probe is a crucial factor for a gas detection unit correct functioning In order to obtain the maximum r...

Page 4: ...The probe detects an anomaly FAULT 1 2 3 4 5 6 C NO C NO C NO Fault Relay Pre Allarme Relay Pre Allarme Relay Optional Relay Card CARD03 Linear Output 4 20 mA 100 20 100 20 SELECTION OF THE OPERATING RANGE The SGM595 Conventional Probes NOT SUITABLE IN ATEX ZONE LEAVE THE FACTORY WITH A DEFAULT OPERATING RANGE VALUE SET AT 20 OF THE LEL To select the operation range to 100 LEL you need to move the...

Page 5: ...mise the safety of the survey If the device does not start up Check that the 12 24 Vdc power is present and that positive and negative polarity has not been inverted If the Fault LED lights up Check that the cables are connected according to the drawing and that the wire isolation sheath has not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26...

Page 6: ...nce and gas sensor replacement Detectiondiagrams data ppm 0 50 100 150 200 250 300 6 7 Toxic Gas Detection diagram 0 4 5 10 15 20 7 2 20 m A Linear 5 Zona Avaria 9 3 12 14 6 17 3 Explosive Gas Detection diagram 0 4 8 12 16 20 0 4 5 10 15 20 7 2 10 4 13 6 16 8 20 m A Linear 5 L I E Zona Avaria The installation of the SGM595 probe its ordinary and extraordinary maintenance and its out of service rem...

Page 7: ... stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the gener...

Page 8: ...shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicab...