Power Supply   ..................................................................................................... 12÷24VDC         ± 10%
Power demand ................................................................. 90 mA in operating, 110 mA in alarm Max @ 13,8 V
Rapports.......................................................... green light normal operation, yellow light fault, red light alarm
Slot exspansion board relay; CARD-03 .......................  Fault , Prealarm, Allarm. Relay contacts 1A 30 VDC  SELV

Sensor    ...............................................................................................................................  Cartalityc
Sensitive element  working  range    ......................................................................................  To  100%  of LEL
Analog output signal  ...................................................................................... 4÷20 mA standard tolerance
Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector  accuracy  .....................................................................................................................  1%  FS
Long  term shift in clean air   ...................................................................................................  < 3% of LEL
Auto  zero  procedure    ............................................................................  Included  in  the  software algorithms
Response  Time    ............................................................................................................................  <10”
Warm-up  time  ...................................................................................................................  1,30  minutes
Functioning  humidity    .............................................................................................  0-90%  non  condensed
Functioning  temperature    ................................................................................................  -10°C  to  +50°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280,  BX150, GS300-Mc, BX316xp, BX308xp
Max.  distance  between  probe  and  unit    ..........................................................................................  100  m
Cable  diameter  for  connecting  probe    ..............................................................................................  1  mm

Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s  body  material    ....................................................................................................................  ABS
External  degree  of  protection    ........................................................................................................  IP55
Size    ..............................................................................................................................78x114x58  mm

WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 50 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year,  by a  qualified
technician.

CHECK  the  integrity  of  the  unit  after  having  removed  it  from  the  box.
Check  that  the  data  written  on  the  box  correspond  to  the  type  of  gas  used.
When  doing  the  electrical  connections,  follow  the  drawing  closely.
Any  use  of  the  detector  for  purposes  other  than  the  intended  one  is  considered  improper,  and
as  a  result  of  which  BEINAT S.r.l.  therefore  disclaims  any  responsibility  for  possible  damages
caused  to  people,  animals  or  objects.

TERMS  and  EXPECTATIONS:  The  installation  of  the  SGM595  Sensor,  its  ordinary  and
extraordinary  maintenance,  every  six  months,  and its  out  of  service removal  at  the  end of  the
functional  life  guaranteed  by  the  manufacturer,  must  be  carried  out  by  authorized  or
specialized  personnel.

Do  not  allow  it  to  become  wet.
The  control  unit  can  be  seriously  damaged  as  it  is  not  waterproof  either  when  immersed  in  water  or  exposed
to  high  levels  of  humidity.

Do  not  drop  it.
Heavy  knocks  or  falls  during  transportation  or  installation  can  damage  the  appliance.

Avoid  abrupt  temperature  fluctuations.
Sudden  temperature  variations  can  cause  condensation  and  the  control  unit  could  work  poorly.

Cleaning
Never  clean  the  device  with  chemical  products.  If  necessary,  wash  with  a  moist  cloth.

Precautions

Technical  Specifications

Technical Features  SGM595

Code

 

         Type of Gas

                      Sensor

               Working range           Temperature

SGM595met

Methane

        Catalytic

    LEL 0-100%

-10+50°C

SGM595lpg

LPG

        Catalytic

    LEL 0-100%

-10+50°C

SGM595ldr

Hydrogen

          Catalytic

    LEL 0-100%

-10+50°C

Summary of Contents for SGM595

Page 1: ...ith one of BEINAT s industrial type Control Units detects the presence of esplosive gas such as Methane LPG Hydrogen The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it but also allows execution of a self diagnosis and therefore an AUTOMATIC CALIBRATION in order to always have the maximum detection accuracy The self calibration means...

Page 2: ... gas by issuing it from a pre calibrated testing aerosol Important The test of operation and eventually offset cancellation must be performed at least once a year by a qualified technician CHECK the integrity of the unit after having removed it from the box Check that the data written on the box correspond to the type of gas used When doing the electrical connections follow the drawing closely Any...

Page 3: ... operation of the control unit by spraying a suitable test gas at the base of the probes connected until the alarm condition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel The position of the probe is a crucial factor for a gas detection unit correct functioning In order to obtain the maximum r...

Page 4: ...The probe detects an anomaly FAULT 1 2 3 4 5 6 C NO C NO C NO Fault Relay Pre Allarme Relay Pre Allarme Relay Optional Relay Card CARD03 Linear Output 4 20 mA 100 20 100 20 SELECTION OF THE OPERATING RANGE The SGM595 Conventional Probes NOT SUITABLE IN ATEX ZONE LEAVE THE FACTORY WITH A DEFAULT OPERATING RANGE VALUE SET AT 20 OF THE LEL To select the operation range to 100 LEL you need to move the...

Page 5: ...mise the safety of the survey If the device does not start up Check that the 12 24 Vdc power is present and that positive and negative polarity has not been inverted If the Fault LED lights up Check that the cables are connected according to the drawing and that the wire isolation sheath has not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26...

Page 6: ...nce and gas sensor replacement Detectiondiagrams data ppm 0 50 100 150 200 250 300 6 7 Toxic Gas Detection diagram 0 4 5 10 15 20 7 2 20 m A Linear 5 Zona Avaria 9 3 12 14 6 17 3 Explosive Gas Detection diagram 0 4 8 12 16 20 0 4 5 10 15 20 7 2 10 4 13 6 16 8 20 m A Linear 5 L I E Zona Avaria The installation of the SGM595 probe its ordinary and extraordinary maintenance and its out of service rem...

Page 7: ... stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the gener...

Page 8: ...shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicab...

Reviews: