Power Supply ..................................................................................................... 12÷24VDC ± 10%
Power demand ................................................................. 90 mA in operating, 110 mA in alarm Max @ 13,8 V
Rapports.......................................................... green light normal operation, yellow light fault, red light alarm
Slot exspansion board relay; CARD-03 ....................... Fault , Prealarm, Allarm. Relay contacts 1A 30 VDC SELV
Sensor ............................................................................................................................... Cartalityc
Sensitive element working range ...................................................................................... To 100% of LEL
Analog output signal ...................................................................................... 4÷20 mA standard tolerance
Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector accuracy ..................................................................................................................... 1% FS
Long term shift in clean air ................................................................................................... < 3% of LEL
Auto zero procedure ............................................................................ Included in the software algorithms
Response Time ............................................................................................................................ <10”
Warm-up time ................................................................................................................... 1,30 minutes
Functioning humidity ............................................................................................. 0-90% non condensed
Functioning temperature ................................................................................................ -10°C to +50°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280, BX150, GS300-Mc, BX316xp, BX308xp
Max. distance between probe and unit .......................................................................................... 100 m
Cable diameter for connecting probe .............................................................................................. 1 mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s body material .................................................................................................................... ABS
External degree of protection ........................................................................................................ IP55
Size ..............................................................................................................................78x114x58 mm
WARNING!
The CATALITIC sensor has a life span of 5 to 6 years in clean air.
The working temperature of the probe recommended is from -10 ° C to + 50 ° C.
Every puffy snapshot of gas over 100% of L.I.E. Takes months off the sensor.
Each immediate puff of gas that exceeds 100% of L.E.L. takes away months of life from the sensor.
The detector must be tested by simulating the presence of gas by issuing it from a pre-calibrated testing aerosol.
Important:
The test of operation and eventually offset cancellation must be performed at least once a year, by a qualified
technician.
CHECK the integrity of the unit after having removed it from the box.
Check that the data written on the box correspond to the type of gas used.
When doing the electrical connections, follow the drawing closely.
Any use of the detector for purposes other than the intended one is considered improper, and
as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible damages
caused to people, animals or objects.
TERMS and EXPECTATIONS: The installation of the SGM595 Sensor, its ordinary and
extraordinary maintenance, every six months, and its out of service removal at the end of the
functional life guaranteed by the manufacturer, must be carried out by authorized or
specialized personnel.
Do not allow it to become wet.
The control unit can be seriously damaged as it is not waterproof either when immersed in water or exposed
to high levels of humidity.
Do not drop it.
Heavy knocks or falls during transportation or installation can damage the appliance.
Avoid abrupt temperature fluctuations.
Sudden temperature variations can cause condensation and the control unit could work poorly.
Cleaning
Never clean the device with chemical products. If necessary, wash with a moist cloth.
Precautions
Technical Specifications
Technical Features SGM595
Code
Type of Gas
Sensor
Working range Temperature
SGM595met
Methane
Catalytic
LEL 0-100%
-10+50°C
SGM595lpg
LPG
Catalytic
LEL 0-100%
-10+50°C
SGM595ldr
Hydrogen
Catalytic
LEL 0-100%
-10+50°C