Operation  of  the  TS1008  Tester
By  connecting  the  TS1008  tester,  you  can  proceed  to  check  the  probe  in  question  and  print  the  test  report.

ADC  80  16  (125  145)
probe  sg-O

2

100

sn  24ad12
date  15  2014
DaY  2190
cy  5
al  15
drift  12
range  20
lel  20%  (fault)
print
tar
new  save
low  bat

Edit

Enter

TS1008

Se ns or

Analy ze r

*

%

2

UP              Down

L EL 2 0

Connections  Tester  TS1008

Attention!!
The  regulations  described  in  this  paragraph  must  performed  be  authorized  and  specialized
technician  are  suceptibile  to  compromise  the  safety  of  the  survey.

If  the  device  does  not  start  up.
Check  that  the  12/24  Vdc  power  is  present,  and  that  positive  and  negative  polarity  has  not  been  inverted.

If  the  Fault  LED  lights  up.
Check  that  the  cables  are  connected  according  to  the  drawing,  and  that  the  wire  isolation  sheath  has  not  been
pinched.
Check  the  voltage  at  the  terminals  1-2.  It  must  be  higher  than  10,80  Vdc  and  lesser  than  26,4  Vdc.
Check  that  the  connector  of  the  sensor  is  correctly  inserted.

If  it’s  connected  to  control  unit.  Check  the  voltage  at  the  terminals  2-3.  It  must  be  from  a  minimum  of
0.8  Vdc  to  a  maximum  of  1.1  Vdc.

Remark

.

If  the probes  are connected  to  the control  units    BX308 and  BX316  the  voltage  at  the  terminals  2  and 3  must
be  from  a  minimum  of  0.6  to  a  maximum  of  0.75  VDC

If   othe r  p rob le ms  arise ,  a  sp e cialise d   and /or  authorise d   te chnician  and /or  the   Distrib utor  of
BEINAT  S.r.l.  should  be  contacted  directly.

WARNING.

These  measurement  should  be  performed  in
clean  air.

Moreover,  this  test  must  be  performed  only
with  the  probe  connected  to  a  control  unit,  or
with  a  220  Ohm  resistance  installed  between
terminal  2  and  terminal  3.

.

Troubleshooting before  calling  a  technician

Linear Otput 4-20 mA

3    2    1

R

0

1

3

2

1,1

V.

Vol tmeter

Power  Supply
    12÷24  V.

Summary of Contents for SGM595

Page 1: ...ith one of BEINAT s industrial type Control Units detects the presence of esplosive gas such as Methane LPG Hydrogen The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected to it but also allows execution of a self diagnosis and therefore an AUTOMATIC CALIBRATION in order to always have the maximum detection accuracy The self calibration means...

Page 2: ... gas by issuing it from a pre calibrated testing aerosol Important The test of operation and eventually offset cancellation must be performed at least once a year by a qualified technician CHECK the integrity of the unit after having removed it from the box Check that the data written on the box correspond to the type of gas used When doing the electrical connections follow the drawing closely Any...

Page 3: ... operation of the control unit by spraying a suitable test gas at the base of the probes connected until the alarm condition is reached At least once a year make a more accurate check by a specialist technician Disabling the detector must be carried out by qualified personnel The position of the probe is a crucial factor for a gas detection unit correct functioning In order to obtain the maximum r...

Page 4: ...The probe detects an anomaly FAULT 1 2 3 4 5 6 C NO C NO C NO Fault Relay Pre Allarme Relay Pre Allarme Relay Optional Relay Card CARD03 Linear Output 4 20 mA 100 20 100 20 SELECTION OF THE OPERATING RANGE The SGM595 Conventional Probes NOT SUITABLE IN ATEX ZONE LEAVE THE FACTORY WITH A DEFAULT OPERATING RANGE VALUE SET AT 20 OF THE LEL To select the operation range to 100 LEL you need to move the...

Page 5: ...mise the safety of the survey If the device does not start up Check that the 12 24 Vdc power is present and that positive and negative polarity has not been inverted If the Fault LED lights up Check that the cables are connected according to the drawing and that the wire isolation sheath has not been pinched Check the voltage at the terminals 1 2 It must be higher than 10 80 Vdc and lesser than 26...

Page 6: ...nce and gas sensor replacement Detectiondiagrams data ppm 0 50 100 150 200 250 300 6 7 Toxic Gas Detection diagram 0 4 5 10 15 20 7 2 20 m A Linear 5 Zona Avaria 9 3 12 14 6 17 3 Explosive Gas Detection diagram 0 4 8 12 16 20 0 4 5 10 15 20 7 2 10 4 13 6 16 8 20 m A Linear 5 L I E Zona Avaria The installation of the SGM595 probe its ordinary and extraordinary maintenance and its out of service rem...

Page 7: ... stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and call the emergency services when outside fire department distributors etc IMPORTANT The operation test should not be carried out with the gas tap as this does not guarantee a sufficient concentration to activate the gener...

Page 8: ...shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicab...

Reviews: