background image

Page 9 of 9

Instruction Manual A75  Version 6   19th April 2004

BEKA associates Ltd,  Old Charlton Road,   Hitchin,   Hertfordshire.   SG5 2DA.   UK.   Tel: +44 (0) 1462 438301

4 seconds. The tare value is stored even if there is a power
failure.

10) - Troubleshooting

There is no display. 

Check all the connections are correctly

made and check the power supply for the correct rating.

I have changed the input type, and no longer have a
sensible reading. 

Make sure you have changed over the

input connectors for example, changing an input from 4-20mA
to 0-10V will require the input to be changed from terminals
3&4 to 1&4.

The display is not very bright/too bright.

 Adjust the

brightness by pressing and holding the up or down button.
(Section 9.1.3)

Display doesn’t seem to be responding to a change of
input signal. 

Check the input signal. It may also be possible

that someone has accidentally re-calibrated the unit to display
the same value over the full input range – check the span and
zero settings in the “cAL” parameters (Section 8.5.6) – if
necessary re-calibrate with the “Int” (internal) settings.
Alternatively, the internal references may have been
accidentally reset – re-program them. (Section 8.5.7)

None of the pushbuttons seem to be working. 

It may be

that the pushbuttons have been disabled (i.e. anti-tamper
function has been switched on). Enter the button re-enable
sequence. (Section 8.7)

The display is too “jumpy”. 

Check the signal source, it may

be noisy. If the signal source cannot be “damped” down,
change the resolution of the Advisor. (Section 8.5.2)

I’ve forgotten my password – how do I get access ?

 Enter

“FPAc” (the emergency code – mnemonic “Forgotten Panel
Access Code”) and re-enter a new password in “F.PAn” menu
option. (Section 8.5.9)

The alarms are on when they should be off and vice
versa.

 Check the high and low alarm settings (Section 8.6.4)

and/or check you have the normally energized (“nE”)
parameter correctly programmed (Section 8.6.5)

The analogue output current doesn’t seem to be correct.

The analogue output can be adjusted. (Section 8.5.8)

The transducer supply output is higher than expected.

Remember, the transducer supply output is a 4 wire output
i.e. 2 supply lines and 2 sense lines. The sense lines must be
connected either directly to the sensor or to the supply
outputs otherwise the Advisor will “hunt” for a sensor and the
output voltage will seem to be excessive. (See section 8.8)

11) Typical Applications

A Position Sensor (0-10V input signal)

Tank Level Display (4/20mA Active Sensor)

Transmitter has its own power supply

Temperature Display (4/20mA Passive – Loop-
powered Transmitter)

24Vdc transmitter power supply option fitted

Weight Display (15Vdc Transducer supply
output, 0-100mV input range)

Transducer power supply fitted.

Summary of Contents for Advisor A75

Page 1: ... 8 1 General 8 2 Button Functions In Programming Mode 8 3 General Programming Structure 8 4 Main Programming Menu Flowchart 8 5 Sub Menu Programming 8 5 1 Square Root Extractor 8 5 2 Display Resolution 8 5 3 Decimal Point 8 5 4 Max and Min Hold 8 5 5 Display Units or Percentage 8 5 6 Calibration Internal or External Source 8 5 7 Setting Internal References 8 5 8 4 20mA Analogue Output 8 5 9 Front ...

Page 2: ...sor panel meters The A75 has been designed specifically to display voltage or current process signals in engineering units It is a microprocessor based instrument and consequently simple to use The Advisor A75 has a user selectable input range The power supply is selected at the time of ordering Each Advisor has a display brightness control and max min hold already included in the internal softwar...

Page 3: ...gain local control by following the key press sequence as outlined in section 8 7 8 2 Button Functions In Programming Mode To enter Programming Mode press the scroll and return buttons together When the instrument is supplied the security access password is set to 0000 If this password has not been changed then the operator is given immediate access to the programming mode If the password has been...

Page 4: ...Page 4 of 9 Instruction Manual A75 Version 6 19th April 2004 BEKA associates Ltd Old Charlton Road Hitchin Hertfordshire SG5 2DA UK Tel 44 0 1462 438301 8 4 Main Programming Menu Flowchart ...

Page 5: ...ode with this parameter On the max and min values stored can displayed by pressing the up and down buttons and reset by pressing the up and down buttons together The maximum and minimum values will be lost on power failure 8 5 5 U P Display Units or Percentage In Normal Display Mode the scroll button can be programmed to give one of two readings either the actual signal input in its own units or t...

Page 6: ...put from 0 10V to 4 20mA the display should also be re calibrated as outlined in section 8 5 6 Table 1 Choice of input range and the corresponding rAng settings Input Range rAng Setting 0 100mV 0 1u 0 200mV 0 2u 0 500mV 0 5u 0 1V 1u 0 2V 2u 0 5V 5u 0 10V 10u 0 20mA 0 02A 0 50mA 0 05A 1 5V 1 5u 4 20mA 4 20 10 50mA 10 50 8 5 8 Iout 4 20mA Analogue Output If fitted This parameter allows the 4 20mA an...

Page 7: ...ion allows the relay outputs to be de activated or silenced for up to 3600 seconds Hence an alarm sounder connected to the output relays could be momentarily silenced by the operator pressing the scroll button If the input signal is still in the alarm range after the silence time had elapsed the alarm is automatically re activated 8 6 8 Ltch Latch This function allows the alarms to be latched on I...

Page 8: ...regularly change alarm setpoints without having to go through all the programming menus To access the alarm setpoints if the function has been switched on in program mode see section 8 6 9 the up and scroll buttons should be pressed simultaneously The operator will then be able to access setpoints SP1 and SP2 by pressing the up button New setpoints can then be entered with the up down and scroll b...

Page 9: ...e been disabled i e anti tamper function has been switched on Enter the button re enable sequence Section 8 7 The display is too jumpy Check the signal source it may be noisy If the signal source cannot be damped down change the resolution of the Advisor Section 8 5 2 I ve forgotten my password how do I get access Enter FPAc the emergency code mnemonic Forgotten Panel Access Code and re enter a ne...

Reviews: