background image

30

APPENDIX 2
ATEX dust certification

In  addition  to  ATEX  certification  permitting
installation  in  Zone  2  gas  atmospheres  which  is
described  in  the  main  section  of  this  instruction
manual,  the  BA307NE  and  the  BA327NE  also
have ATEX Ex tc certification, allowing installation
in  Zone  22  combustible  dust  atmospheres  when
mounted in an Ex t panel enclosure.

A2.1

Zones and Maximum Surface
Temperature

Both  indicators  have  been  certified  as  Group  II
Category 3D Ex tc IIIC T80°C Dc IP20 apparatus
with a Ta of  –40°C to +70C.  This is dust ignition
protection  by  enclosure  complying  with
BS  EN  60079-31

 Equipment  dust  ignition

protection by enclosure "t".

When  mounted  in  an  Ex  t  panel  enclosure  as
specified in section 5 of this instruction manual and
complying  with  the  installation  requirements  of
BS EN 60079-14 the indicators may be installed in:

Zone 22

explosive atmosphere in the form of
a cloud of combustible dust in air is
not  likely  to  occur  in  normal
operation,  but  if  it  does  occur,  will
only persist for a short period.

Be used with dusts having a Minimum Ignition 
Temperature of:

Dust cloud

120°C

Dust layer on indicator 

155°C

up to 5mm thick. 

*

Dust layer on indicator 

Refer to

over 5mm thick. 

*

BS EN 60079-14

At an ambient temperature between -40 and +70°C

*

  Unlikely occurrence in Zone 22

A2.2  Installation 

All the circuits shown in the main section of this
manual  for  indicator  installations  in  Zone  2
flammable gas atmospheres, may also be used for
Zone  22  combustible  dust  applications.        The
indicator  should  be  installed  in  an  Ex t  panel
enclosure  located  within  Zone  22.      The  panel
enclosure  containing  the  indicator  should  be
located  where  the  minimum  amount  of  dust  will
accumulate on them and the installation should be
as specified in section 5 of this instruction manual
and comply with the requirements of EN 60079-14

.

BS EN 60079-14 requires that each of the wires
entering the hazardous area should be individually
fused and contain a means of isolation.  However,
in practice instrumentation energised by a current
limited  power  supply  that  can  be  switched  off  is
often considered adequate.

A2.3  Maintenance

The BA307NE and BA327NE front panel keypads
are  intrinsic  safe  Ex ic  which  allows  them  to  be
operated in Zone 22

.

The  IEC  guidance  on  maintenance  procedures
EN 60079-17 permits live maintenance in Zone 22
if a risk analysis demonstrates that this does not
introduce  an  unacceptable  risk.   The  removal  of
covers [opening of Ex tc enclosure] is permitted if
this can be done without contaminating the interior
of  the  enclosure  and  instrument  with  dust  or
moisture.    Some  end-users  may  prefer  not  to
permit live maintenance to minimise risk.

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

Live  maintenance  within  the  hazardous
area should only be performed when it is
permitted by risk analysis or when there
is  no  risk  of  a  flammable  atmosphere
being present.

Before  closing  the  Ex tc  enclosure
ensure  that  the  sealing  gaskets  are
undamaged  and  free  from  dirt  and
foreign bodies.

Inspection of

  t

he indicator’s mechanical condition

and removal of accumulated dust from the front of
the indicator and the outside of the Ex tc enclosure
should  be  performed  regularly.  The  interval
between inspections depends upon environmental
conditions.   Removal of flammable dust should be
performed with care to avoid creating a dust cloud.

Summary of Contents for BA307NE

Page 1: ...Issue 3 1st Novemeber 2017 BA307NE BA327NE Ex nA Ex tc loop powered panel mounting indicators Issue 3...

Page 2: ...figuration 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Scale...

Page 3: ...European ATEX Directive 94 9 EC The certificate number has an X suffix indicating that the two indicators are subject to special condition for safe use For installations in Zone 2 the panel enclosure...

Page 4: ...both instruments with a common Type Examination Certificate number ITS14ATEX48028X This has been used to confirm compliance with the European ATEX Directive for Group II Category 3GD equipment The in...

Page 5: ...roups Group A propane Group B ethylene Group C hydrogen In gases that may safely be used with equipment having a temperature classification of T1 450o C T2 300o C T3 200o C T4 135o C T5 100o C At ambi...

Page 6: ...ea should be individually fused and contain a means of isolation These two requirements are frequently satisfied by using switch fuse holders with easily removable fuses which can be extracted to achi...

Page 7: ...is a satisfactory method at the low voltages and currents common in instrumentation systems Clear identification of and easy access to the means of isolation is essential for their effective use It i...

Page 8: ...el enclosure cut out dimensions Fig 4 Dimensions 5 2 Installation Procedure a Cut the aperture specified in Fig 4 in the panel enclosure Ensure that the edges of aperture are de burred b Inspect the i...

Page 9: ...ard showing the requested units of measurement if this information is not supplied when the indicator is ordered a blank card will be fitted A pack of self adhesive scale cards printed with common uni...

Page 10: ...10...

Page 11: ...uration BA307NE BA327NE Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA Zero 0 0 0 00 Display at 20mA SPAn 100 0 100 00 Resolution rESn 1 digit 1 digit Bargraph start BarLo 0 00...

Page 12: ...in 16 segment adjustable lineariser To reveal the existing indicator function select FunC from the configuration menu and press P If the function is set as required press E to return to the menu or pr...

Page 13: ...tween the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the i...

Page 14: ...rompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code which must be entered to gain access New instruments...

Page 15: ...e This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this me...

Page 16: ...16...

Page 17: ...to the required value before the P button is operated to enter the required indicator display Error message If during calibration the indicator displays a FAiL error message the current at which the s...

Page 18: ...oints has been defined and then return to the in sub function by pressing the E button The corresponding indicator display at each of the break points can now be defined using the diSP sub function Us...

Page 19: ...rior of the instrument with dust or moisture Some end users may prefer not to permit live maintenance to minimise risk ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance within the hazar...

Page 20: ...the enclosure panel being distorted or creeping when the indicator panel clamps are tightened and ensures that the joint between the indicator and the panel enclosure in which it is mounted remains se...

Page 21: ...ed in Zone 2 is displaying the output from an Flameproof Ex d 2 wire transmitter located in Zone 1 Alarm 1 is switching an Ex e sounder in Zone 1 and alarm 2 is switching a sounder located in the safe...

Page 22: ...22...

Page 23: ...ndicator display equals the setpoint See section 9 4 5 Hi Lo Alarm function Defines the alarm function as High or Low See section 9 4 6 no nC Normally open or normally closed output Sets the alarm out...

Page 24: ...r fail safe operation both alarm outputs should be conditioned to be open in the alarm condition nC To check or change the alarm output status select no nC from the alarm configuration menu and press...

Page 25: ...ving access to the indicator configuration menu Protection against accidental adjustment of the setpoints when the indicator is in the display mode is provided by a separate security code This direct...

Page 26: ...int plus the displayed value to be represented or a low and a high setpoint plus the displayed value to be represented by the bargraph as shown in Fig 16 Fig 16 Displayed value and setpoints on bargra...

Page 27: ...o or greater than 9V At lower supply voltages the backlight will continue to function but with reduced brilliance and will draw less current The ATEX certificate therefore only specifies the maximum s...

Page 28: ...re four design requirements 1 The indicator should be installed generally as shown in section 5 and Fig 20 2 The certificate specifies that the indicator should be connected to a limited energy 4 20mA...

Page 29: ...Fig 21 2 The four vents at the rear of the indicator enclosure shown in Fig 22 must not be obstructed 3 The certificate specifies that the indicator should be connected to a limited energy 4 20mA circ...

Page 30: ...ne 22 The panel enclosure containing the indicator should be located where the minimum amount of dust will accumulate on them and the installation should be as specified in section 5 of this instructi...

Page 31: ...X 4 ETL cETL certification for installations in USA and Canada A4 0 cETL Mark For installations in the USA and Canada the BA307NE and BA327NE indicators have ETL and cETL Ex nA and Ex tc approval Cont...

Reviews: