background image

11

When all the digits have been adjusted, press 

E

 to

enter the new zero.  The indicator will display 'Ent'
for a few seconds while the information is being
stored in memory, and will then return to the 'ZErO'
prompt .

To adjust the display at 20mA, press the 

Up

 button

which will cause the indicator to display 'SPAn'.
Adjust the external current calibrator to 20.000mA
and again press 

P

  which will reveal the existing

full scale display.   Each digit of the indicator
display can be changed by pressing the 

Up

 or

Down

 buttons. When the first digit is correct,

pressing 

P

 will transfer control to the next digit.

When all the digits have been adjusted press 

E

 to

enter the new span.  The indicator will display 'Ent'
for a few seconds while the information is being
stored in memory, and will then return to the
'SPAn' prompt.  Finally press 

E

 again to return to

the main menu.

This function may also be used when calibrating a
complete loop from primary element to indicator
display e.g. when the indicator is displaying the
output from a resistance thermometer transmitter.

6.6 Calibration of display using internal

references:   SEt

This function enables the zero and span of the
indicator to be adjusted without the need for an
accurate external current source, or for
disconnection from the 4/20mA loop.  The
accuracy of this method depends upon the
accuracy of the internal references which should
be regularly calibrated as described in section
6.7.2

To calibrate the indicator select 'SEt' from the main
menu and press 

P

.  The indicator will display

'ZErO', pressing 

P

 again will reveal the current

display at 4mA.   Each digit of the indicator display
can be changed by pressing the 

Up

 or 

Down

buttons. When the first digit is correct, pressing 

P

will transfer control to the next digit.  When the
least significant digit has been adjusted, press 

E

 to

return to the 'ZErO' prompt which completes the
adjustment.

To adjust the display at 20mA, press the 

Up

 button

which will cause the indicator to display 'SPAn'.
Pressing 

P

 again will reveal the indicator display.

Each digit can be changed by pressing the 

Up

 or

Down

 buttons. When the first digit is correct,

pressing 

P

 will transfer control to the next digit.

When the least significant digit has been adjusted
press 

E

 to return to the 'SPAn' prompt followed by

E

 to return to the menu.

6.7  Conditioning sub-menu:   Cond

This sub-menu allows the mains (line) frequency at
which the indicator has maximum ac rejection to
be selected and the two internal references to be
calibrated.  These functions are contained in a
sub-menu to minimise the possibility of inadvertent
adjustment.  To gain access to the sub-menu
select 'Cond'  from the main menu and press 

P

.

The indicator will display 'SurE' to warn that
changing the parameters in the sub-menu will
change the indicator display.  Pressing 

P

 again will

give access to the sub-menu, or pressing 

E

 will

return the indicator to the main menu.

6.7.1  AC rejection:   FrE

Caution

If the mains filter frequency is
changed, the indicator display and
internal references (if used) must
be recalibrated.

To provide maximum low frequency rejection the
internal digital filter may be set to operate at 50 or
60Hz to correspond with the local mains (line)
frequency.   To change the frequency select 'FrE'
from the 'Cond' sub-menu and press 

P

 which will

reveal the current setting.  The setting can be
changed by pressing the 

Up

 or 

Down

 buttons

followed by the 

E

 button to return to the sub-menu.

6.7.2  Calibration of internal references:  rEF

The indicator contains two references representing
4 and 20mA.  These references are used in the
'SEt' function which enables the indicator display to
be calibrated without an external current calibrator.
They are also used in the 'C--P' function when the

P

 push-button is programmed to display the input

current in the display mode.   If neither of these
functions is to be used, it is not necessary to
calibrate the internal references.

To calibrate the references select 'rEF' from the
sub-menu and press 

P

  which will result in a

'0.004A' prompt being displayed. Adjust the
external current calibrator to 4.000mA  and again
press 

P

 .  The indicator will display 'Ent' when the

4mA reference has been updated and will then
return to the '.004A' prompt.

To re-calibrate the 20mA internal reference, press
the 

Up

 button which will cause the indicator to

display '.020A'. Adjust the external current
calibrator to 20.000mA  and again press 

P

 . The

indicator will display 'Ent' when the 20mA
reference has been updated and will then return to
the '.020A' prompt.  Two operations of the 

E

 button

will return the indicator to the main menu.

Summary of Contents for BA324ND

Page 1: ...Issue 7 4th March 2014 BA324ND Type nL certified loop powered 4 digit field mounting indicator Issue 7 Only for replacement use after May 2013 Use BA324NE for new applications...

Page 2: ...eferences 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Units o...

Page 3: ...forward biased diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which...

Page 4: ...60079 Part 14 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted 3 3 4 20mA input terminals Input terminal...

Page 5: ...Fig 2 BA324ND in a transmitter loop In practice it is only necessary to ensure that in normal operation the maximum current flowing in the loop is less than 30mA In the example shown in Fig 2 this cu...

Page 6: ...ted to the internal EMC filters For maximum radio frequency interference rejection this terminal should be connected to a local earth or to a cable screen which is earthed in the safe area To prevent...

Page 7: ...and may be operated when a flammable atmosphere is likely to be present All the programming functions are contained in an easy to use menu which is shown diagramatically in Fig 6 Each function is sum...

Page 8: ...s the resolution of the least significant display digit May be set to 1 2 5 or 10 digits See section 6 3 d P Decimal point Positions the dummy decimal point between any of the digits or turns it off S...

Page 9: ...ial flowmeter Below 5 of flow the BA324ND display is forced to zero of full flow Current output mA 5 0 4 04 10 0 4 16 25 0 5 00 50 0 8 00 75 0 13 00 100 0 20 00 6 3 Resolution rESn This function defin...

Page 10: ...10...

Page 11: ...least significant digit has been adjusted press E to return to the SPAn prompt followed by E to return to the menu 6 7 Conditioning sub menu Cond This sub menu allows the mains line frequency at whic...

Page 12: ...ith the default security code 0000 which allows unrestricted access to all programming functions To enter a new security code select COdE from the menu and press P which will cause the indicator to di...

Page 13: ...and press E to return to the main menu Step 4 Select frequency of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the...

Page 14: ...y of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the FrE function Using the Up or Down buttons select 50 and then...

Page 15: ...ay has a large voltage ripple content Unable to Incorrect Enter correct security enter the security code or fit security programme code link in override position Mode entered See Fig 7 8 2 Fault findi...

Page 16: ...intenance The mechanical condition of the instrument and electrical calibration should be regularly checked The interval between inspections depends upon environmental conditions We recommend that ini...

Page 17: ...A324ND can also be supplied with a blank or custom engraved stainless steel plate secured to the instrument terminal cover by two screws 9 2 Alarms The BA324ND can be supplied with two solid state sin...

Page 18: ...owing table summarises each of the alarm programme functions and includes a cross reference to more detailed information Again only the functions on alarm 1 are listed but alarm 2 has identical facili...

Page 19: ...een calibrated to display 0 with 4mA input and 10000 with 20mA input the two alarm setpoints may be positioned anywhere between 125 and 10125 To adjust the setpoint select SP1 or SP2 from the alarm me...

Page 20: ...can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 2 8 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been c...

Page 21: ...nt AcSP This function controls a separate menu which provides direct access to the alarm setpoints when the indicator is in the display mode See section 9 2 12 for a full description An operator may t...

Page 22: ...ressing E will return the display to the SP1 or SP2 prompt from which the other setpoint may be selected or the indicator may be returned to the display mode by pressing E again Direct access to the a...

Page 23: ...n can be selected using the Up and Down push buttons The delete break point function dEL operates in a similar manner to the Add function described above When the required number of break points has b...

Page 24: ...24...

Page 25: ...equired break point has been selected press P to reveal the existing display Using the Up and Down buttons and P to move between digits set the revised display Press E to return to the sub menu from w...

Page 26: ...i 30V dc Ii 100mA dc Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 15 Providing the supply voltage is less than 30V the backlight safety componen...

Page 27: ...re available for securing the BA324ND to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any pipe with outside diameter between 60 and 8...

Reviews: