7.2 Using the internal references
As in 7.1 the BA324ND is required to display:
-50.0
with a 4mA input
1050.0
with a 20mA input
from a linear transducer. Maximum display
resolution is required, the frequency of the mains
supply is 50Hz and the existing security code is
1209. In the operating mode the indicator is
required to display the input current in milliamps
when the P push-button is operated.
This example assumes that the internal references
have been routinely calibrated.
Step1
Enter the programming mode
With an input current between 4 and
20mA put the indicator in the
programming mode by simultaneously
pressing
P
and
E
. The indicator will
respond by displaying 'COdE'. Press
P
to clear this prompt and set the
display to the security code 1209
using the
Up
,
Down
and
P
push-
buttons. Pressing
E
will enter the
code, and after a few seconds during
which the decimal points will be
scrolled, the first parameter 'root' in
the main menu will be displayed.
Step 2
Square root extractor
With 'root' displayed, press
P
which
will reveal the root extractor status.
The root extractor can be turned on or
off by the
Up
or
Down
buttons. Select
'OFF', and press
E
to return to the
main menu.
Step
3
Select frequency of maximum
mains (line) rejection
Scroll though the main menu until
'Cond' is displayed. Enter the sub-
menu by pressing
P
twice and select
the 'FrE' function. Using the
Up
or
Down
buttons select '50', and then
press
E
twice to return to the main
menu.
Step 4
Define function of P push-button
Select 'C--P' from the main menu and
press
P
to reveal the function of the
P
button in the display mode. Select '4-
20' and return to the main menu by
pressing
E
.
Step 5
Position dummy decimal point
Select 'd.P' from the main menu and
then press
P
. Using the
Up
and
Down
push-buttons position the
dummy decimal point in front of the
least significant digit.
Press
E
to return to the main menu.
Step 6
Calibrate display
With any input current between 4 and
20mA select 'SEt' from the main menu
and press
P
. The indicator will
display 'ZErO' in the sub-menu; press
P
to reveal the existing zero display.
Using the
Up
,
Down
and
P
push-
buttons enter the required zero
display of -50.0 Press
E
to return to
the 'ZErO' prompt.
Again with any input current between
4 and 20mA press the
Up
push-button
and the indicator will display 'SPAn'.
Press
P
to reveal the existing span
display. Using the
Up
,
Down
and
P
push-buttons enter the required span
display of 1050.0 Press
E
to return
to the 'SPAn' prompt. Press
E
again to
return to the main menu.
Step 7
Return to display mode
Following completion of calibration
return to the display mode by pressing
E
.