background image

22

9.2.12 Adjusting alarm setpoints from the

display mode

Access to the alarm setpoints from the indicator
display mode is obtained by operating the 

P

 and

Up

 push-buttons simultaneously as shown in Fig

12.  If the setpoints are not protected by a security
code the alarm setpoint  prompt 'SP1' will be
displayed.  If the setpoints are protected by a
security code, 'COde' will be displayed first.
Pressing 

P

 again will enable the alarm security

code to be entered digit by digit using the 

Up

 and

Down

 buttons to change the flashing digit, and the

P

 push-button to move to the next digit.  If the

correct code is entered pressing 

E

 will cause alarm

setpoint prompt 'SP1' to be displayed.  Pressing
the 

Up

 or 

Down

 button will toggle the display

between the two alarm setpoint prompts 'SP1' and
'SP2'.

If an incorrect security code is entered, or a button
is not pressed within ten seconds, the indicator will
automatically return to the display mode.

Fig 12 Setpoint adjustment from the display mode

To adjust an alarm setpoint select 'SP1' or 'SP2'
and press 

P

 which will reveal the current setting.

Each digit of the setpoint may be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

P

 button

to move to the next digit.

When the required setpoint has been entered,
pressing 

E

 will return the display to the 'SP1' or

'SP2' prompt from which the other setpoint may be
selected, or the indicator may be returned to the
display mode by pressing 

E

 again.

Direct access to the alarm setpoints is only
available when the  menu is enabled - see section
9.2.11

9.3  Lineariser

The indicator can be supplied with a sixteen point
lineariser which may be adjusted to compensate
for almost any non linear variable.  For example, a
level signal from a horizontal cylindrical tank may
be linearised by the indicator to display the tank
contents in linear volumetric units.

The addition of linearising software does not affect
the intrinsic safety of the indicator.

Fig 13 shows a typical linearising characteristic.
Up to sixteen break-points may be programmed to
occur at any input current between 4 and 20mA.
The slope between adjacent break-points may be
set anywhere between -1250 and +1250 display
counts per milliamp.  Greater slopes may be
programmed, but the indicator performance will be
degraded.  A linear characteristic can be obtained
by programming just two points, one at 4mA and
the other at 20mA.

Fig 13   Typical indicator characteristic

The lineariser software does not change the main
programme menu, but the 'CAL' and 'SEt' functions
are extended as shown in  Fig 14.    As with a
linear indicator, calibration may be performed with
an external calibrator using the 'CAL' function,  or
from the internal references using the 'Set'
function.

Summary of Contents for BA324ND

Page 1: ...Issue 7 4th March 2014 BA324ND Type nL certified loop powered 4 digit field mounting indicator Issue 7 Only for replacement use after May 2013 Use BA324NE for new applications...

Page 2: ...eferences 8 Maintenance 8 1 Fault finding during commissioning 8 2 Fault finding after commissioning 8 3 Servicing 8 4 Routine maintenance 8 5 Guarantee 8 6 Customer comments 9 Accessories 9 1 Units o...

Page 3: ...forward biased diode D1 The voltage developed across D1 which is relatively constant is multiplied by a switch mode power supply and used to power the instrument The voltage developed across R1 which...

Page 4: ...60079 Part 14 Electrical Installation in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice should be consulted 3 3 4 20mA input terminals Input terminal...

Page 5: ...Fig 2 BA324ND in a transmitter loop In practice it is only necessary to ensure that in normal operation the maximum current flowing in the loop is less than 30mA In the example shown in Fig 2 this cu...

Page 6: ...ted to the internal EMC filters For maximum radio frequency interference rejection this terminal should be connected to a local earth or to a cable screen which is earthed in the safe area To prevent...

Page 7: ...and may be operated when a flammable atmosphere is likely to be present All the programming functions are contained in an easy to use menu which is shown diagramatically in Fig 6 Each function is sum...

Page 8: ...s the resolution of the least significant display digit May be set to 1 2 5 or 10 digits See section 6 3 d P Decimal point Positions the dummy decimal point between any of the digits or turns it off S...

Page 9: ...ial flowmeter Below 5 of flow the BA324ND display is forced to zero of full flow Current output mA 5 0 4 04 10 0 4 16 25 0 5 00 50 0 8 00 75 0 13 00 100 0 20 00 6 3 Resolution rESn This function defin...

Page 10: ...10...

Page 11: ...least significant digit has been adjusted press E to return to the SPAn prompt followed by E to return to the menu 6 7 Conditioning sub menu Cond This sub menu allows the mains line frequency at whic...

Page 12: ...ith the default security code 0000 which allows unrestricted access to all programming functions To enter a new security code select COdE from the menu and press P which will cause the indicator to di...

Page 13: ...and press E to return to the main menu Step 4 Select frequency of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the...

Page 14: ...y of maximum mains line rejection Scroll though the main menu until Cond is displayed Enter the sub menu by pressing P twice and select the FrE function Using the Up or Down buttons select 50 and then...

Page 15: ...ay has a large voltage ripple content Unable to Incorrect Enter correct security enter the security code or fit security programme code link in override position Mode entered See Fig 7 8 2 Fault findi...

Page 16: ...intenance The mechanical condition of the instrument and electrical calibration should be regularly checked The interval between inspections depends upon environmental conditions We recommend that ini...

Page 17: ...A324ND can also be supplied with a blank or custom engraved stainless steel plate secured to the instrument terminal cover by two screws 9 2 Alarms The BA324ND can be supplied with two solid state sin...

Page 18: ...owing table summarises each of the alarm programme functions and includes a cross reference to more detailed information Again only the functions on alarm 1 are listed but alarm 2 has identical facili...

Page 19: ...een calibrated to display 0 with 4mA input and 10000 with 20mA input the two alarm setpoints may be positioned anywhere between 125 and 10125 To adjust the setpoint select SP1 or SP2 from the alarm me...

Page 20: ...can be changed by pressing the Up or Down button followed by the E button to return to the alarm menu 9 2 8 Hysteresis HStr During programming hysteresis is shown in the units the indicator has been c...

Page 21: ...nt AcSP This function controls a separate menu which provides direct access to the alarm setpoints when the indicator is in the display mode See section 9 2 12 for a full description An operator may t...

Page 22: ...ressing E will return the display to the SP1 or SP2 prompt from which the other setpoint may be selected or the indicator may be returned to the display mode by pressing E again Direct access to the a...

Page 23: ...n can be selected using the Up and Down push buttons The delete break point function dEL operates in a similar manner to the Add function described above When the required number of break points has b...

Page 24: ...24...

Page 25: ...equired break point has been selected press P to reveal the existing display Using the Up and Down buttons and P to move between digits set the revised display Press E to return to the sub menu from w...

Page 26: ...i 30V dc Ii 100mA dc Pi 1 3W This allows the backlight to be powered from a safe area 18 to 30V dc supply as shown in Fig 15 Providing the supply voltage is less than 30V the backlight safety componen...

Page 27: ...re available for securing the BA324ND to a horizontal or vertical pipe BA392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any pipe with outside diameter between 60 and 8...

Reviews: